Belden 9327 Cable 22 AWG 27 Pairs Overall Beldfoil Shield Audio Control and Instrumentation Multi Conductor Solid PVC Jacket Cable

Belden 9327 Cable 22 AWG 27 Pairs Overall Beldfoil Shield Audio Control and Instrumentation Multi Conductor Solid PVC Jacket Cable

Precio habitual $17.00 $14.00 Oferta /per Foot

Belden 9327 Cable 22 AWG 27 Pairs Overall Beldfoil Shield Audio Control and Instrumentation Multi Conductor Solid PVC Jacket Cable

Description:
• 22 AWG solid tinned copper conductors, PVC insulation, twisted pairs, overall Beldfoil shield (100% coverage), 22 AWG stranded TC drain wire, PVC jacket.

Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.3302

Outer Shield Drain Wire AWG:
• AWG: 22
• Stranding: 7x30
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.143

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -20°C To +80°C
• UL Temperature Rating: 80°C (UL AWM Style 2464)
• Bulk Cable Weight: 215 lbs/1000 ft.
• Max. Recommended Pulling Tension: 428 lbs.
• Min. Bend Radius/Minor Axis: 6.250 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Inductance (μH/ft): 0.2
• Nom. Capacitance Conductor to Shield (pF/ft): 50
• Nom. Capacitance Conductor to Conductor (pF/ft): 35
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 16.5
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 12.5
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 1.4 Amps/Conductor @ 25°C

Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• CSA Flame Test: FT4

Plenum/Non-Plenum:
• Plenum (Y/N): No

technical specification:
awg 22
# pairs 27
stranding solid
no. of conductors 54
conductor material tinned copper
outer shield - type tape
outer shield - material aluminum foil-polyester tape
overall cable- nominal dia. (mm) 15.621
belden cable part number 9327

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question