2.4KV UL Type MV 105, MC-HL, CT, 105, EPR Insulation - HW309 00203

2.4KV UL Type MV 105, MC-HL, CT, 105, EPR Insulation - HW309 00203

2.4KV UL TYPE MV 105, MC-HL, CT, 105, EPR INSULATION - HW309 00203
Technical Specifications:
Catalog Number HW309 00203
Size AWG/kcmil 2
No. of Conductors 3
No. of Strands 7
Insulation Thickness Mils 90
Jacket Thickness Mils 50
Ground Wire Size No.- AWG 3-10
Class 1 Div. 2 Connector No. 416MA05V
Rain Tight Connector No. 416MC06
Armor Diameter Inch 1.33
Overall Diameter Inch 1.44
Net Weight Lbs/Mft 1215

Specifications:

  • Impervious Continuously Welded Armor - Power Cable
  • 2.4KV UL Type MV 105, MC-HL, CT Use, 105°C
  • Non-Shielded, EPR Insulation
  • 133% Insulation Level
  • Aluminum Armor
  • Copper Conductors

Application:
For use in harsh environments where maximum conductor protection is required. Used for primary power and feeder circuits in a broad range of commercial and industrial power distribution systems. Approved for use in wet or dry locations at 105°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 2400 volts. May be used in NEC Class I and II, Division 2 and Class III, Division 1 and 2 hazardous locations. National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions. Impervious continuously welded and corrugated aluminum armor cable is recommended as an economical alternative to wire in conduit systems.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-96-659.

Grounding Conductor: Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL 1072.

Armor:
Impervious continuously welded and corrugated aluminum.

Jacket:
Yellow flame-retardant and sunlight-resistant PVC.

Flame Tests:

ICEA 70,000 BTU/hr and 210,000 BTU/hr flame test

Color Code:

ICEA Method 4

Additional Standards:

  • NEMA WC 71
  • UL 1309 listed as Marine Shipboard Cable

Connectors:

  • Explosion Proof, Class I Division 1: 424MA series - exterior components - aluminum, interior components - nickel-plated brass
  • Rain Tight: 416MC series - all nickel-plated brass
  • See 424MA series in Section J.