General Cable EmPowr® 15 kV 220Mils 750kcmil Longitudinally Applied Corrugated Tape 1.846 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
Select gauge from drop-down menu for prices:
- General Cable EmPowr® 15 kV Longitudinally Applied Corrugated Tape LLDPE Jacket Fill Shielded Power Cable Al Conductor EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 250kcmil Longitudinally Applied Corrugated Tape 1.264 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 250kcmil Longitudinally Applied Corrugated Tape 1.270 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 350kcmil Longitudinally Applied Corrugated Tape 1.367 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 350kcmil Longitudinally Applied Corrugated Tape 1.373 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 500kcmil Longitudinally Applied Corrugated Tape 1.495 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 500kcmil Longitudinally Applied Corrugated Tape 1.515 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 750kcmil Longitudinally Applied Corrugated Tape 1.696 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 750kcmil Longitudinally Applied Corrugated Tape 1.702 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 1000kcmil Longitudinally Applied Corrugated Tape 1.905 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 175Mils 1000kcmil Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 250kcmil Longitudinally Applied Corrugated Tape 1.354 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 250kcmil Longitudinally Applied Corrugated Tape 1.360 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 350kcmil Longitudinally Applied Corrugated Tape 1.457 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 350kcmil Longitudinally Applied Corrugated Tape 1.463 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 500kcmil Longitudinally Applied Corrugated Tape 1.599 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 500kcmil Longitudinally Applied Corrugated Tape 1.605 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 750kcmil Longitudinally Applied Corrugated Tape 1.852 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 1000kcmil Longitudinally Applied Corrugated Tape 1.995 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
- General Cable EmPowr® 15 kV 220Mils 1000kcmil Longitudinally Applied Corrugated Tape 2.001 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation
Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Corrugated copper tape and an extruded black jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable.
Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.
Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer.
Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III.
Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation.
Longitudinally Applied Corrugated Tape: Copper, 8 or 10 mil thick Longitudinally Applied Corrugated Tape (LACT) with a minimum 375 mil overlap.
Jacket: Black, non-conducting, sunlight-resistant, Linear Low-Density Polyethylene (LLDPE).
Features and Benefits:
• Even distribution of fault current and better heat dissipation
• Allows expansion/contraction of cable core
• Improved bending characteristics versus helical copper tape shield
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Flexibility for easy handling
• Excellent moisture resistance
• Deformation-resistant
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield without the use of a release agent
• Sunlight-resistant
Temperature Rating:
• Normal - 105°C
• Emergency* - 140°C
• Short Circuit - 250°C
Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.
Options:
• Copper conductors
• EmPowr® Fill LF Lead-Free EAM
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• BIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT
• TRIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT 3. sealed overlap and blocked LACT/jacket
• Sealed LACT overlap
• Dry nitrogen cure
• True Triple Extrusion
• Red stripes on jacket
• Semi-conducting thermoplastic jacket
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• UL Listed
technical specifications: | |
compressed conductor(al awg or kcmil) | 750 |
compressed conductor(no. of wires) | 61 |
diameter (1) inches(insulation in min.) | 1.430 |
diameter (1) inches(insulation in max.) | 1.520 |
diameter (1) inches(lact shield - thkn.) | 0.008 |
diameter (1) inches(lact shield - o.d.) | 1.626 |
diameter (1) inches(lldpe jacket) | 1.846 |
nominal jacket thkn. inches(1) | 0.110 |
approx. weight (1) lb/1000 ft(al cond) | 703 |
pprox. weight (1) lb/1000 ft(cu shield)
|
203 |
approx. weight (1) lb/1000 ft(total) | 1871 |
ampacity (2)(direct buried) | 665 |
ampacity (2)(in duct) | 530 |