Technical data:
• Control cable of special-PUR to UL CSA AWM I/II A/B Style 20939 (sheath insulation) and CSA

Temperature range
• flexing -5°C to +80°C
• fixed installation -40°C to +80°C

Nominal voltage
• UL/CSA 600 V

Test voltage
• 3000 V

Breakdown voltage
• min. 6000 V

Insulation resistance
• min 20 MOhm x km

Minimum bending radius
• flexing 7,5x cable Ø
• fixed installation 4x cable Ø

Radiation resistance
• up to 100x106 cJ/kg (up to 100 Mrad)

Cable structure:
• Bare copper, fine wire stranded to DIN VDE 0295 cl.5, BS 6360 cl.5 and IEC 60228 cl.5
• Core insulation of PVC compound type TI3 to DIN VDE 0207-363-3 / DIN EN 50363-3 and UL-Style 10012
• Core identification to DIN VDE 0293 black cores with continuous white numbering
• GN-YE conductor, 3 cores and above in the outer layer
• Cores stranded in layers with optimal lay-length
• Outer sheath of special full-polyurethane
• Sheath colour grey (RAL 7001)
• with meter marking

Properties:
• Resistant to mineral oils, synthetic oils, coolant, UV-radiation, oxygene, ozon and hydrolysis. Conditionally resistant to microbes.
• The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Note:
• G = with green-yellow conductor
• x = without green-yellow conductor (OZ)
• AWG sizes are approximate equivalent values. The actual cross-section is in mm².
• unscreened analogue type: JZ-602-C-PUR

Application:
• UL and CSA approved flexible control cable rated at 600 V, primarily designed for exporters to the US or Canadian market. Used in machine tools, control systems, connection between control panels and machines, assembly lines and other industrial equipment. Suitable for installation in dry, moist, wet and outdoor environment and moderate flexing applications.

technical specification:
awg-no 12
no.cores x cross-sec. mm² 4 G 4
outer ø app. mm 12,4
cop. weight kg/km 154,0
weight app. kg/km 298,0
helukabel part number 12517