General Cable HVTECK® 6 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
Select gauge from drop-down menu for prices:
- General Cable HVTECK® 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 4 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 2 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 1 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 1/0 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 2/0 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 3/0 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 4/0 AWG 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 250MCM 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 350MCM 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 500MCM 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 750MCM 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
- General Cable HVTECK® 1000MCM 90 Mils 1C TRXLPE Wire Shield PVC AIA PVC Power Shielded Armored 5 kV CSA
Conductor: 6 AWG thru 1000 kcmil bare copper compact Class B strand
Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor
Insulation: Tree-Retardant Cross-linked Polyethylene (TRXLPE)
Insulation Shield: Black semi-conducting thermosetting layer, applied in a triple extrusive process, plus a concentric serving of solid copper wires acting as both a drain wire shield and a grounding (bonding) conductor
Ground (Bonding) Conductor: The conductor is a concentric serving of solid copper wires applied over the thermosetting insulation shield
Inner Jacket: Lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
Armor: Aluminum Interlocked Armor (AIA)
Overall Jacket: Lead-free, ACID-FLAME-CHECK ??® flameretardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armor (GSIA)
Applications:
• For wiring in all hazardous locations when used with certified HL cable glands
• For exposed and concealed wiring in dry, damp or wet locations
• For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required by inspection authority)
Features:
• Rated at 90?C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Cost-effective alternative to installations in conduit
• Meets cold bend and impact tests at -40?C
Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 131 and No. 174
• CSA Standard C68.10
Flame Test Compliances:
• CSA FT1 and FT4
• IEEE 383 (70,000 BTU/hr)
• UL 1581 (70,000 BTU/hr)
• IEEE 1202 (70,000 BTU/hr) CSA FT4
• ICEA T-30-520 (70,000 BTU/hr)
• ICEA T-29-520 (210,000 BTU/hr)
Other Compliances:
• Hazardous Location Rating: HL
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
• RoHS Compliant
Packaging:
• For Canadian customers, lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for lagging, pulling eyes, paralleling and plexing
• For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing
technical specification: | |
cond. size (awg/kcmil) | 6 |
no. of cond. | 1 |
ground wire size (awg) | 8 |
nominal diameter (over)(insulation in inches) | 0.39 |
nominal diameter (over)(insulation in mm) | 10.0 |
nominal diameter (over)(insulation shield in inches) | 0.47 |
nominal diameter (over)(insulation shield in mm) | 11.9 |
nominal diameter (over)(inner jacket in inches) | 0.68 |
nominal diameter (over)(inner jacket in mm) | 17.3 |
nominal diameter (over)(armor in inches) | 0.90 |
nominal diameter (over)(armor in mm) | 22.9 |
nominal diameter (over)(cable in inches) | 0.99 |
nominal diameter (over)(cable in mm) | 25.2 |
copper weight(lbs/1000 ft) | 144 |
copper weight(kg/km) | 214 |
net weightw/al armor(lbs/1000ft) | 510 |
net weight w/al armor(kg/km) | 770 |
outdoor ampacity** (40?c ambient) | 112 |