HW292 HL Listed CIR® Instrumentation Cable Individually Shielded Triads + Ground 0.6/1kV 90°C Gexol® Insulation - 16 AWG -12 Triads
Select gauge from drop-down menu for prices:
- HW292 HL Listed CIR® Instrumentation Cable Individually Shielded Triads + Ground 0.6/1kV 90°C Gexol® Insulation
- HW292 HL Listed CIR® Instrumentation Cable Individually Shielded Triads + Ground 0.6/1kV 90°C Gexol® Insulation - 16 AWG - 1 Triad
- HW292 HL Listed CIR® Instrumentation Cable Individually Shielded Triads + Ground 0.6/1kV 90°C Gexol® Insulation - 16 AWG - 4 Triads
- HW292 HL Listed CIR® Instrumentation Cable Individually Shielded Triads + Ground 0.6/1kV 90°C Gexol® Insulation - 16 AWG - 8 Triads
Technical Specifications: | |
Catalog Number/HWC Part # | HW292 01612 |
Size AWG | 16 |
Size (mm2) |
1.3 |
Triads | 12 |
Nominal Diameter (inches) | 1.395 |
Weight (lbs./1000 ft.) | 1235 |
DC Resistance at 20°C (Ohms/1000 ft.) | 4.52 |
Mutual Capacitance (nF/1000 ft.) | 32 |
Inductance (mH/1000 ft.) | 0.2 |
HL Listed | -- |
Specifications:
- HW292
- HL Listed CIR® Instrumentation Cable*
- Individually Shielded Triads + Ground
- 0.6/1kV 90°C Gexol® Insulation
Application:
Designed and constructed to be a flexible alternative
to Type MC cable where crush and impact protection in
arctic conditions is required.
Conductors:
Soft annealed flexible stranded tinned copper per
IEEE 1580 Table 11.
Insulation:
Gexol cross-linked flame retardant polyolefin, meets
requirements for Type P of IEEE 1580 and Type X110 of UL
1309/CSA 245. 600V/IEC 1000V
Shielding:
Each pair/triad is twisted with a bare tinned drain wire. Each
pair/triad is shielded with polyester-backed aluminum foil tape
to afford 100% coverage. Pair to pair or triad to triad, isolation –
plus overall shielding – is provided.
Grounding Conductor:
Soft annealed, flexible stranded, uninsulated, tinned copper sized
in accordance with UL 1277.
Jacket:
A black, flame retardant, oil, abrasion, chemical and sunlight
resistant thermoset compound meeting UL 1309/CSA 245 and
IEEE 1580.
Ratings & Approvals :
- 90°C temperature rating
- UL Listed as Marine Shipboard Cable (E111461)
- UL Listed as Type TC-ER
- UL Listed as Type TC-ER-HL*
- American Bureau of Shipping (ABS) (99-BT5905-X)
- Flame Retardant – IEEE 1202
- Suitable for use in Class I, Div 2 & Zone 2 environments
- Suitable for use in Class I, Div 1 & Zone 1 environments*
- *Cables up to 1” in OD
Features:
- Complies with the requirements for TC-ER-HL* per UL 2225
- Gas & vapor tight – impervious to water and air
- Smaller bend radius (up to 40% smaller) than Type MC
- Reduced tray fill (up to 35% less) compared to Type MC
- Considerably more flexible than Type MC
- Brittle point as per ASTM D 746-07 exceeds -65°C for Jacket and -75°C for Insulation
- Exceeds CSA cold bend / cold impact (-40°C / -35°C)
Instrumentation Cable Color Legend: |
|
Pairs | Black, White |
Triads | Black, White, Red |