General Cable Instrumentation Cable 18/2 Gauge Overall Shield 600V VW-1 ULTROL® 60+

General Cable Instrumentation Cable 18/2 Gauge Overall Shield 600V VW-1 ULTROL® 60+

Select gauge from drop-down menu for prices:

General Cable Instrumentation Cable 18/2 Gauge Overall Shield 600V VW-1 ULTROL® 60+

Conductor: 18 AWG and 16 AWG tinned annealed copper per ASTM B33; Class B stranding per ASTM B8

Insulation:
• Flame-retardant, heat-, moisture- and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE)
• Color code: Per ICEA Method 1, Table E-1

Overall Shield: Copper/polyester tape in contact with a stranded tinned copper drain wire

Jacket: Flame-retardant, moisture-, oil-, sunlightand radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyolefin (XLPO) ­­— Black

Print: GENERAL CABLE (WC) ULTROL® 60+ XX/C XXAWG COPPER FR-XLPE XLPO SHIELDED 600 V 90°C SUN RES OIL RES I & II DIR BUR NUCLEAR DAY MONTH YEAR TRACEABILITY NUMBER SEQUENTIAL FOOTAGE MARK

Options:
• Conductor stranding
• ISO Metric conductors
• Tinned copper braid shield

Applications:
• ULTROL® 60+ instrumentation cable is a 600 V overall shielded multi-conductor, thermoset, Class 1E rated construction specifically designed for applications in nuclear generating stations and where flame retardancy is critical
• Designed for use on circuits where overall shielding is required to protect from external electrostatic interference
• Can be installed in trays, conduit, ducts, or in direct burial applications

Features:
• Rated at 90°C wet or dry
• Fully traceable
• Qualified for 60-year service life
• Gamma and beta radiation resistant (up to 350 megarads)
• Submergence operability
• Long-term thermal endurance and superior electricals
• Excellent mechanical cut-through properties
• Long-term moisture and radiation stability
• Free stripping for ease of termination
• Meets cold bend test at -40°C

Industry Compliances:
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003
• ICEA S-73-532

Flame Test Compliances:
• IEEE 383:1974
• IEEE 383:2003
• ICEA T-29-520
• IEEE 1202/FT4-1991, Aged & Unaged
• VW-1

Other:
• Quality assurance program in accordance with NRC 10CFR50 Appendix B
• ANSI N45.2
• ASME NQA-1
• NIAC
• NUPIC

Packaging: Material to be shipped on non-returnable wooden reels

technical specifications:
cond. size (awg) 18
no. of cond. 2
cond. strand 7/.0152
minimum avg. insulation thickness(inches) 0.025
minimum avg. insulation thickness(mm) 0.64
drain wire size (awg) 20
minimum avg. jacket thickness(inches) 0.045
minimum avg. jacket thickness(mm) 1.14
nominal cable o.d.(inches) 0.291
nominal cable o.d.(mm) 7.39
copper weight(lbs/1000ft) 13
copper weight(kg/km) 20
net weight(lbs/1000ft) 57
net weight(kg/km) 85
catalog number 22560.18.2