Plenum Fire Alarm Cable Solid Foil Shielded - Power Limited Fire Protective Cable - Data Grade Low Capacitance - 12 AWG - 8 Cond.

Plenum Fire Alarm Cable Solid Foil Shielded - Power Limited Fire Protective Cable - Data Grade Low Capacitance - 12 AWG - 8 Cond.

Select gauge from drop-down menu for prices:

Plenum Fire Alarm Cable Solid Foil Shielded - Power Limited Fire Protective Cable - Data Grade Low Capacitance - 12 AWG - 8 Cond.

Product Details

Technical Specifications:
Aero P/N 6810K
AWG 12
No. of Cond. 8
Insulation Thickness (inches) .012
Jacket Thickness (inches) .015
Jacket O.D. (inches) .454
Lbs/1000' 223

Specifications:

  • Plenum Fire Alarm Cable Solid Foil Shielded
  • Power Limited Fire Protective Cable: [ Foil Shielded, FPLP: 18 thru 12 AWG, Data Grade Low Capacitance (150°C) ]
  • Plenum / Solid / Shielded. (UL) FPLP, 150°C.

Conductor:
Solid BC

Insulation:
FEP

Color Code:
Chart 1

Shield:
Aluminum/Mylar

Jacket:
Halar E-CTFE

Industry Approvals:

  • NEC Article 760-FPLP

Impedance:

  • (AWG 18) 50 Ohms Nom.
  • (AWG 16) 43 Ohms Nom.
  • (AWG 14) 42 Ohms Nom.
  • (AWG 12) 37 Ohms Nom.

Vel. of Propagation:

  • 69% Nom.

Capacitance:

  • (AWG 18) 30 pF/FT Nom.
  • (AWG 16) 35 pF/FT Nom.
  • (AWG 14) 36 pF/FT Nom.
  • (AWG 12) 40 pF/FT Nom.

Temperature Rating:

  • -40°C to +150°C

Put Ups:

  • 1000 Feet (+/- 10%) (Available in Bulk Reels)

Additional Notes:

  • NON-CONDUIT