General Cable Power Cable 8/3 Gauge with Ground 600V VW-1 UL Type TC-ER ULTROL® 60+

General Cable Power Cable 8/3 Gauge with Ground 600V VW-1 UL Type TC-ER ULTROL® 60+

Select gauge from drop-down menu for prices:

General Cable Power Cable 8/3 Gauge with Ground 600V VW-1 UL Type TC-ER ULTROL® 60+

Conductor: 8 AWG thru 750 kcmil tinned annealed copper per ASTM B33; Class B stranding per ASTM B8

Insulation: 
• Flame-retardant, heat-, moisture- and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE) 
• Color code: Per ICEA Method 1, Table E-1

Grounding Conductor: Tinned annealed copper Class B stranding, sized according to NEC® requirements

Jacket: Flame-retardant, moisture-, oil-, sunlightand radiation-resistant thermoset ULTROL® 60+ Cross-linked Polyolefin (XLPO) — Black 

Options: 
• Conductor stranding 
• ISO Metric conductors 
• Colored insulation 
• Method 4 color code 
• Sectioned grounding conductors 
• Longitudinal corrugated tinned copper tape shield 

Applications: 
• ULTROL® 60+ power cable is a 600 V multi-conductor, thermoset, Class 1E rated construction specifically designed for applications in nuclear generating     stations and where flame retardancy is critical 
• For use in Class 1E power distribution and control circuits for power lighting, control and signal circuits 
• Can be installed in trays, conduit, ducts, or in direct burial applications 

Features: 
• Rated at 90?C wet or dry 
• Fully traceable 
• Qualified for 60-year service life 
• Gamma and beta radiation resistant (up to 350 megarads) 
• Submergence operability 
• Long-term thermal endurance and superior electricals
• Excellent mechanical cut-through properties 
• Long-term moisture and radiation stability 
• Free stripping for ease of termination 
• Meets cold bend test at -40°C 

Industry Compliances: 
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003 
• ICEA S-73-532 
• UL 1277 Type TC-ER 
• UL 44 XHHW-2 

Flame Test Compliances: 
• IEEE 383:1974 
• IEEE 383:2003 
• ICEA T-29-520 
• IEEE 1202/FT4-1991, Aged & Unaged 
• VW-1 

Other: 
• Quality assurance program in accordance with NRC 10CFR50 Appendix B 
• ANSI N45.2 
• ASME NQA-1 
• NIAC 
• NUPIC 

Packaging: Material to be shipped on spools on nonreturnable wooden reels

technical specifications:
cond.size(awg/kcmil) 8
no. of cond. 3
cond.strand 7/.0486
minimum avg.insulation thickness(inches) 0.045
minimum avg.insulation thickness(mm) 1.14
ground wire size(awg) 10
minimum avg.jacket thickness(inches) 0.060
minimum avg.jacket thickness(mm)
1.52
nominal cable o.d.(inches) 0.629
nominal cable o.d.(mm) 16.0
copper weight(lbs/1000 ft) 187
copper weight(kg/km) 278
net weight(lbs/1000 ft) 328
net weight(kg/km) 488
catalog number 32560.8.3

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question