Prysmian and Draka Cable 1 Core 70 Cross-section Core RU(c) 0.6/1kV Earthing Cable 840084

Prysmian and Draka Cable 1 Core 70 Cross-section Core RU(c) 0.6/1kV Earthing Cable 840084

Prysmian and Draka Cable 1 Core 70 Cross-section Core RU(c) 0.6/1kV Earthing Cable 840084

Conductor: Tinned stranded circular copper, BS6360, class 2

Insulation: EP-rubber, GP4 to BS7655:section 1.2

Inner sheath: No inner sheath, additional tapes may be applied

Armour/screen: No armour

Outer sheath: Flame retardant, halogen-free, enhanced oil resisting thermoset compound (LSF) SW4 to BS7655 section 2.6. (Mud resistant version availabe on request)

Marking text: "metre mark" "year" "DRAKA" "RU" "UKOOA code" "600/1000V" number of cores" "conductor size" "BS6883" "IEC60332-3-22" (marking may differ on cable actually supplied)

Outer sheath colour: Green/Yellow

Core Identification: Single core - off white

Operating temperature: 90°C

Operating Voltage: 0.6/1kV

Standards applied:
• BS6883 - Design
• BS6360 class 2 - Conductor
• BS7655 section 1.2 - Insulation
• BS7655 section 2.6 - Sheath
• IEC 60332-1 - Flame Retardant
• IEC60332-3-22 - Flame retardant
• IEC60754-1,2 - Halogen Free
• IEC 61034-1,2 - Low Smoke

Description:
• RU 0.6/1kV 1X 6mm2
• RU 0.6/1kV 1X 16mm2
• RU 0.6/1kV 1X 25mm2
• RU 0.6/1kV 1X 35mm2
• RU 0.6/1kV 1X 70mm2

Sheath Colour: Yellow/Green

Design standard: BS 6883:1999

Application:
• Unarmoured cable for fixed installation for earthing purposes in safe areas.
• Enhanced MUD resistant version also available for use in areas exposed to mud and drilling / cleaning fluids, meeting the mud resistance requirement in NEK 606.

technical specification:
number of cores 1
cross section core, mm2 70
conductor diameter, mm 10.85
insulation thickness, mm 1.4
thickness outer sheath, mm 1.3
approx. overall diameter, mm 16.5
approx. weight of cable (kg/km) 820
copper content approx. (kg/km) 620
max. conductor resistance at 20°c, ohm/km 0.27
max. conductor resistance at 90°c, ohm/km 0.344
current rating iec 60092-352 table b.4, ampere 242
short circuit rating 1 second, ampere 9800
prysmian and draka cable part number 840084