Prysmian Cable 1000 MCM CU Single Conductor Airguard CSA 35kV 133% Medium Voltage Commercial, Industrial Cables QXM305A

Prysmian Cable 1000 MCM CU Single Conductor Airguard CSA 35kV 133% Medium Voltage Commercial, Industrial Cables QXM305A

Select gauge from drop-down menu for prices:

Prysmian Cable 1000 MCM CU Single Conductor Airguard CSA 35kV 133% Medium Voltage Commercial, Industrial Cables QXM305A
Prysmian Cable 1000 MCM CU Single Conductor Airguard CSA 35kV 133% Medium Voltage Commercial, Industrial Cables QXM305A

Single conductor cable with stranded copper conductor, extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX® EPR insulation, thermosetting semiconducting insulation shield, helically applied bare copper tape shield, separator tape, foamed polymeric Air Bag™ layer for superior mechanical protection, a Drylam® layer consisting of a longitudinally applied aluminum tape and an extruded oil and hydrocarbon resistant polymer, and overall non-leaded sun resistant PVC jacket.

Specifications:
• CSA -CSA C68.10
• CSA - C22.2 No.0.3
• CSA - C22.2 No. 230

Ratings:
• Cold Impact/Bend Test (-40°C) 105°C
• Sunlight Resistant FT4
• TC (1/0 AWG and Larger)

Conductor: Class B Compact concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength EPROTENAX® EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Helically applied non-magnetic copper tape(s) over the insulation shield followed by a separator tape.

Mechanical Protection: High strength and high crush resistant Air Bag™ Layer extruded over the core.

Chemical Protection: A layer of Drylam® which consists of an aluminum tape a chemical resistant extruded polymer layer is applied.

Jacket: Sunlight resistant polyvinyl chloride (PVC), non-leaded jacket.

technical specification
conductor size 1000 MCM CU
insulation thickness (mils) 420
conductor diameter (mm) (A) 27.20
insulation diameter (mm) (B) 49.81
insulation shield diameter (mm) (C) 51.23
overall jacket diameter (mm) (D) 63.45
cable weight (lkg/km) 7621
minimum bending radius (mm) 762
ampacity in air and cable tray‡105°c 1160
impedance in air and cable tray (μω/m) pos/neg seq 71 + j202
impedance in air and cable tray (μω/m)zero seq 953 + j67
prysmian cable part number QXM305A

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question