Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8400ZC

Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8400ZC

Select gauge from drop-down menu for prices:

Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8400ZC
Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8400ZC

Conductor: Solid or Class B compact or compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.

Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes.

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.

Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• EPROTENAX™ (EPR) insulation
• Multiplex cables
• Tinned round and flat strap neutrals
• Strandseal®
• Super smooth conductor shield
• Cables made to AEIC CS8 and/or ICEA S-94-649
• 46kV

Installations:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary

Specifications and Ratings:
• CSA - CSA C68.5 -40°C
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.

technical specifications:
conductor 2 awg cu
insulation thickness (mils) 220
concentric neutral 9-#16
conductor diameter (in) - (a) 6.81
insulation diameter (in) - (b) 19.25
insulation shield diameter (in) - (c) 21.13
jacket diameter (in) - (d) 26.56
cable weight (lbs/kft) 882
minimum bending radius (in) 229
† ampacity (amps) - 90°c in duct 162
+/- sequence impedance resistance (µΩ/ft) - 90°c in duct 0.67
+/- sequence impedance reactance (µΩ/ft) - 90°c in duct 0.17
zero sequence impedance resistance (µΩ/ft)†† - 90°c in duct 2.45
zero sequence impedance reactance (µΩ/ft)†† - 90°c in duct
0.10
† ampacity (amps) - 90°c direct buried 224
+/- sequence impedance resistance (µΩ/ft) - 90°c direct buried 0.70
+/- sequence impedance reactance (µΩ/ft) - 90°c direct buried 0.34
zero sequence impedance resistance (µΩ/ft)†† - 90°c direct buried 2.41
zero sequence impedance reactance (µΩ/ft)††- 90°c direct buried 0.10
prysmian cable part number Q8400ZC

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question