Teck 90 Armoured Power Shielded Single Conductor 90 MIL 100%/133% 5kV - AWG Size Cond 4

Teck 90 Armoured Power Shielded Single Conductor 90 MIL 100%/133% 5kV - AWG Size Cond 4

TECK 90 ARMOURED POWER SHIELDED SINGLE CONDUCTOR 90 MIL 100%/133% 5KV - AWG SIZE COND 4
Technical Specifications:
Catalog Number 19002-03-060
AWG Size Cond. 4
AWG Bond Wire
6
Insulation Thickness (in.) 0.090
Approximate Diameter (Over) Insul. (in.) 0.430
Approximate Diameter (Over) Inner Jacket (in.) 0.720
Approximate Diameter (Over) Armour (in.) 0.940
Approximate Diameter (Over) Outer Jacket (in.) 1.030
Copper Content LB/MFT 224
Copper Content KG/KM 333
Net Weight w/ Armour LB/MFT
590
Net Weight w/ Armour KG/ KM 880
Amp. (30°C Ambient) 148

Specifications:

  • Teck 90 Armoured Power
  • Shielded Single Conductor
  • 90 MIL 100%/133% 5kV
  • TR-XLPE/PVC/AIA/PVC
  • CSA FT1 & FT4
  • CSA C22.2 No. 131 & 174
  • CSA C68.3
  • IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
  • ICEA T-29-520 (210,000 BTU/hr) Vertical Flame Test
  • ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test

CONSTRUCTION:

  • Conductor: Bare copper Class B compact or compressed stranded
  • Conductor Shield: Extruded thermoset semi-conducting shield
  • Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
  • Insulation Shield: Extruded thermosetting semi-conducting shield
  • Ground (Bonding) Conductor: Stranded bare copper conductor
  • Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
  • Armour: Aluminum Interlocked Armour (AIA)
  • Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
  • Options: Other coloured outer jacket and constructions available upon request

QUESTIONS & ANSWERS