General Cable ACWU90® 3C 500MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

General Cable ACWU90® 3C 500MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

ACWU90 3C 500MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

Conductor: 6 AWG thru 750 kcmil bare ACM aluminum (8000 series aluminum) compact Class B strand

Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 6 AWG to 2 AWG—black, white and red; 1/0 AWG to 750 kcmil—per ICEA Method 4, individual conductors colored black with conductor number surface printed in contrasting ink

Ground (Bonding) Conductor: The conductor consists of one uninsulated stranded bare aluminum (ACM) conductor

Armor: Aluminum Interlocked Armor (AIA)

Jacket: ACID-FLAME-CHECK ??® flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black

Applications:
• For exposed and concealed wiring in dry, damp or wet locations
• For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required by inspection authority)
• For wiring in all hazardous locations when used with certified HL cable glands
• For service entrance installations

Features:
• Rated at 90°C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Cost-effective alternative to installations in conduit
• Meets cold bend and impact tests at -40°C

Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 51 and No. 174
• CSA Approval File Number 157657

Flame Test Compliances: CSA FT1 and FT4

Other Compliances:
• Hazardous Location Rating: HL
• OSHA Acceptable

Packaging: For Canadian customers, nominal standard lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for cut to length, lagging and pulling eyes

technical specifications:
cond. size (awg/kcmil) 500
cond. strand 37/.125
nominal conductor o.d.(inches) 0.736
nominal conductor o.d.(mm) 18.694
min. avg. insulation thickness(inches) 0.060
min. avg. insulation thickness(mm) 1.524
nominal diameter (over)(insulation in inches) 0.860
nominal diameter (over)(insulation in mm) 21.844
nominal diameter (over)(armor in inches) 2.240
nominal diameter (over)(armor in mm) 56.896
nominal diameter (over)(cable in inches) 2.390
nominal diameter (over)(cable in mm) 60.706
aluminum weight*(lbs/1000 ft) 1491
aluminum weight*(kg/km) 2170
net weight( lbs/1000 ft)
2348
net weight(kg/km) 3417
90?c ampacity** (30°c ambient) 350
catalog number 11281.036500

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.