Belden 9579 Cable 16 AWG 4 Conductors Power Limited Fire Protective Signaling Circuit Solid BC PVC Jacket Cable

Belden 9579 Cable 16 AWG 4 Conductors Power Limited Fire Protective Signaling Circuit Solid BC PVC Jacket Cable

Precio habitual $5.72 $3.81 Oferta /per Foot

Belden 9579 Cable 16 AWG 4 Conductors Power Limited Fire Protective Signaling Circuit Solid BC PVC Jacket Cable

Description:
• 16 AWG solid bare copper conductors, conductors cabled, PVC insulation, overall Beldfoil® shield (100% coverage), 22 AWG stranded TCV drain wire, PVC jacket.

Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.4572

Outer Shield Drain Wire AWG:
• AWG: 22
• Stranding: 7x30
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.0688

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -40°C To +105°C
• UL Temperature Rating: 105°C
• Bulk Cable Weight: 96.733 Kg/Km
• Max. Recommended Pulling Tension: 693.919 N
• Min. Bend Radius/Minor Axis: 82.550 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMR, FPLR
• NEC Articles: 760
• CEC/C(UL) Specification: FAS105
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
• Other Specification: California State Fire Marshall

Electrical Characteristics (Overall):
• Nom. Capacitance Conductor to Conductor (pF/m): 173.893
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/m): 321.538
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 13.4521
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 37.0753
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 11 Amps/Conductor @ 25°C

Flame Test:
• UL Flame Test: UL1666 Vertical Tray
• CSA Flame Test: FT4

Plenum/Non-Plenum:
• Plenum (Y/N): No

technical specification:
awg 16
# conductors 4
stranding solid
no. of conductors 4
conductor material bare copper
outer shield - type tape
outer shield - material aluminum foil-polyester tape
overall cable- nominal dia. (mm) 7.645
belden cable part number 9579

QUESTIONS & ANSWERS