1/0-1/0-2 Brenau Triplex Aluminum URD Cable 600V
Select gauge from drop-down menu for prices:
- Triplex Aluminum URD Direct Burial Wire 600V
- 6-6-6 Erskine Triplex Aluminum URD Cable 600V
- 4-4-4 Vassar Triplex Aluminum URD Cable 600V
- 2-2-4 Stephens Triplex Aluminum URD Cable 600V
- 2-2-2 Ramapo Triplex Aluminum URD Cable 600V
- 1/0-1/0-1/0 Bergen Triplex Aluminum URD Cable 600V
- 2/0-2/0-2/0 Hunter Triplex Aluminum URD Cable 600V
- 2/0-2/0-1 Converse Triplex Aluminum URD Cable 600V
- 3/0-3/0-1/0 Hollins Triplex Aluminum URD Cable 600V
- 3/0-3/0-3/0 Rockland Triplex Aluminum URD Cable 600V
- 4/0-4/0-2/0 Sweetbriar Triplex Aluminum URD Cable 600V
- 4/0-4/0-4/0 Monmouth Triplex Aluminum URD Cable 600V
- 250-250-3/0 Pratt Triplex Aluminum URD Cable 600V
- 350-350-4/0 Wesleyan Triplex Aluminum URD Cable 600V
- 500-500-300 Holyoke Triplex Aluminum URD Cable 600V
- 500-500-350 Rider Triplex Aluminum URD Cable 600V
- 750-750-500 Fairfield Triplex Aluminum URD Cable 600V
Description:
Brenau 1/0-1/0-2 is a three conductor Aluminum URD cable that has two phase conductors and a single neutral wire. The phase conductors have smaller gauge sizes that the neutral. The phase conductors are of 1/0 AWG gauge sizes while the neutral is 2 AWG. This cable is rated for 600 volts and Temperature of 90°C. The current ratings are 215 for direct burial and 160 amps when ducts are used.
Applications:
#1/0-1/0-2 Brenau Aluminum Underground Distribution Cable specifically designed for underground distribution systems. In extreme environmental conditions, the cross-linked polyethylene is used since it can withstand temperatures of up to 90°C.
Conductors:
They are made of aluminum alloy which are compressed in 1350-H19. Only 99.5% of the conductor is made of aluminum the rest is made of zinc, copper and silicon.
Insulation:
The insulation is made of standard polyethylene or cross-linked polyethylene.
Features:
• Can resist high temperatures of up to 90°C
• Corrosion resistant conductors
• Heat and moisture resistant insulation
• Lead free triplex wire
• 600 volt URD cable
Standards:
• ASTM B-901
• ICEA S-105-692
• Federal Specification J-C-30B
• RUS Accepted
Technical Specifications: | |
Phase Conductor Size AWG: | 1/0 |
Phase Conductor Stranding: | 9 |
Phase Conductor Insulation Thickness: | 80 mls |
Base Neutral Messenger Size AWG: | 2 |
Base Neutral Strand: | 7 |
Diameter Single Phase Conductor (Mils): | 512 |
Diameter Complete Cable (O.D.) (Mils): | 1106 |
Weight Per 1000ft Total (Lbs.): | 387 |
Allowable Ampacity 90C (Amps): | 215 |
Allowable Ampacity in Ducts (Amps): | 160 |