500-500-350 Rider Triplex Aluminum URD Cable 600V
Select gauge from drop-down menu for prices:
- Triplex Aluminum URD Direct Burial Wire 600V
- 6-6-6 Erskine Triplex Aluminum URD Cable 600V
- 4-4-4 Vassar Triplex Aluminum URD Cable 600V
- 2-2-4 Stephens Triplex Aluminum URD Cable 600V
- 2-2-2 Ramapo Triplex Aluminum URD Cable 600V
- 1/0-1/0-2 Brenau Triplex Aluminum URD Cable 600V
- 1/0-1/0-1/0 Bergen Triplex Aluminum URD Cable 600V
- 2/0-2/0-2/0 Hunter Triplex Aluminum URD Cable 600V
- 2/0-2/0-1 Converse Triplex Aluminum URD Cable 600V
- 3/0-3/0-1/0 Hollins Triplex Aluminum URD Cable 600V
- 3/0-3/0-3/0 Rockland Triplex Aluminum URD Cable 600V
- 4/0-4/0-2/0 Sweetbriar Triplex Aluminum URD Cable 600V
- 4/0-4/0-4/0 Monmouth Triplex Aluminum URD Cable 600V
- 250-250-3/0 Pratt Triplex Aluminum URD Cable 600V
- 350-350-4/0 Wesleyan Triplex Aluminum URD Cable 600V
- 500-500-300 Holyoke Triplex Aluminum URD Cable 600V
- 750-750-500 Fairfield Triplex Aluminum URD Cable 600V
Description:
Rider 500-500-350 Triplex Aluminum URD cable has 2 phase conductors and a single neutral cable. The phase conductors are slightly bigger than the neutral, they have a 500 MCM gauge size while the neutral has a size of 350 MCM. As a direct burial it transmits up to 495 amps and up to 395 amps in ducts.
Applications:
#500 MCM Rider Underground Distribution Cable specifically designed for underground distribution systems. In extreme environmental conditions, the cross-linked polyethylene is used since it can withstand temperatures of up to 90°C.
Conductors:
They are made of aluminum alloy which are compressed in 1350-H19. Only 99.5% of the conductor is made of aluminum the rest is made of zinc, copper and silicon.
Insulation:
The insulation is made of standard polyethylene or cross-linked polyethylene.
Features:
• Can resist high temperatures of up to 90°C
• Corrosion resistant conductors
• Heat and moisture resistant insulation
• Lead free triplex wire
• 600 volt URD cable
Standards:
• ASTM B-901
• ICEA S-105-692
• Federal Specification J-C-30B
• RUS Accepted
Technical Specifications: | |
Phase Conductor Size AWG: | 500 |
Phase Conductor Stranding: | 37 |
Phase Conductor Insulation Thickness: | 95 mls |
Base Neutral Messenger Size AWG: | 350 |
Base Neutral Strand: | 37 |
Diameter Single Phase Conductor (Mils): | 980 |
Diameter Complete Cable (O.D.) (Mils): | 2217 |
Weight Per 1000ft Total (Lbs.): | 1598 |
Allowable Ampacity 90C (Amps): | 495 |
Allowable Ampacity in Ducts (Amps): | 395 |
Great product, just as described, prompt shipping. Came on several loads. Will use them again.
Great product, just as described, prompt shipping. Came on several loads. Will use them again.