Conductor: 20 AWG fully annealed stranded tinned copper per ASTM B33
Insulation:
• Premium-grade, coIor-coded polyethylene
• Color code: See chart below
Shield:
• 80% tinned copper braid
• Mylar wrap under braid
Jacket:
• PVC, gray
• Temperature range: ?20°C to +75°C
Applications:
• Electronic circuits where RF shielding is required
• Video interconnect
• Broadcast and studio
• Sound systems
• Suggested voltage rating: 300 volts
Compliances:
• NEC Article 800 Type CM/CMH (UL: 75°C)
• AWM style 2092 (UL: 60?C, 300 V)
• AWM style 2093 (UL: 60?C, 300 V)
• AWM style 2094 (UL: 60?C, 300 V)
• RoHS Compliant Directive 2011/65/EU
• Designed to meet UL VW-1 Vertical Wire Flame Test
• CE: Low Voltage Directive (LVD) 2006/95/EC
Packaging: Please contact Customer Service for packaging and color options
technical specifications: | |
awg size | 20 |
no. of cond. | 5 |
cond. strand
|
26/34 |
nom. insulation thickness (inches) | 0.016 |
nom. insulation thickness (mm) | 0.38 |
nom. jacket thickness(inches) | 0.029 |
nom. jacket thickness (mm) | 0.74 |
nominal o.d.(inches) | 0.274 |
nominal o.d.(mm) | 6.96 |
nom. cap.* pf/ft (a) | 22.0 |
nom. cap.* pf/ft (b) | 39.0 |
catalog number | c1645A |