Skip to product information
1 of 1

Prysmian and Draka Cable 6 AWG 266/30 Stranding Bostrail Fire Safe LSZH Single Conductor XLPO jacket 600 Volt Cable F60006

Prysmian and Draka Cable 6 AWG 266/30 Stranding Bostrail Fire Safe LSZH Single Conductor XLPO jacket 600 Volt Cable F60006

SKU: SKU:  

Select a gauge:
  • Prysmian and Draka Cable 6 AWG 266/30 Stranding Bostrail Fire Safe LSZH Single Conductor XLPO jacket 600 Volt Cable F60006
Length: FT
Enter footage in the box - Cut to one length. Min 1 ft - Max 10000 ft.
Sold out
Shipping calculated at checkout.
Shipping Available
Free shipping on orders above $1000. *Wires and cables only.
View full details
Product Information
Prysmian and Draka Cable 6 AWG 266/30 Stranding Bostrail Fire Safe LSZH Single Conductor XLPO jacket 600 Volt Cable F60006

Conductor: The conductor is class “K” stranded in accordance with ASTM B172. The wires are soft, annealed copper with a continuous coating of tin (98.0% conductivity) in accordance with ASTM B33. The conductor resistance meets the requirements of ICEA S-95-658 (NEMA WC70). 

Insulation: Low smoke silicone rubber to comply with appropriate specifications (see chart on back). The insulation fits the conductor tightly but is “clean stripping.” An opaque polyester tape or other suitable separator is used over the conductor. 

Jacket: Flame retardant, low smoke non-halogen and oil resistant crosslinked polyolefin (XLPO) jacket (see chart on back). The jacket is bonded to the EPR insulation. 

Applications: These are single conductor 600 and 2000 volt power cables designed for low-smoke environments such as tunnels and subway systems. They consist of silicone rubber insulated conductor jacketed with a tough low smoke zero halogen (LSZH) crosslinked polyolefin (XLPO) jacket. They are highly heat, oil and moisture-resistant, extremely tough yet Flexible, and can sustain 125°C operating temperatures. 

Ratings: 
• UL 1581 Flame Test 
• IEEE 383 Paragraph 2.5

technical specification:
conductor size 6 AWG
stranding 266/30
voltage rating
600
average insulation/jacket thickness in (mm) .045 (1.1)
bend radius in (mm) 1.20 (30.5)
ampacity* 90°c
105
ampacity* 125°c
127
cable o.d in (mm) 0.305 (7.7)
approximate cable weight lbs/mft (kg/km)
113 (168)
Prysmian and draka cable part number F60006
Reviews