Product Details
Conductor: 2 AWG thru 500 kcmil coated annealed copper, bunched wires, rope-lay-stranded per ASTM B172
Extruded Strand Shield (ESS): Extruded thermosetting semi-conducting stress control layer over conductor
Insulation: Ethylene Propylene Rubber (EPR) insulation colored for contrast with black conducting layer
Insulation Shield: A flexible coated copper/textile braid shield is applied over a conducting overlapped tape
Ground-Check Conductor: Annealed copper, rope-lay-stranded per ASTM B172, insulated with high-strength yellow polypropylene
Grounding Conductors:
• Coated copper, rope-lay-stranded per ASTM B172
• Two conductors in contact with the flexible copper braid shield
Jacket: Reinforced, two-layer, extra-heavy-duty, lead-cured Chlorinated Polyethylene (CPE)
Jacket Marking: GENERAL CABLE® ANACONDA® BRAND (SIZE) 3/C TYPE SHD-GC 15000 VOLTS P-7K-102-046 MSHA
Options:
• Colored jackets are available
• TPU (Thermoplastic Polyurethane) jacket
• Anamaxx® jacket
Applications:
• Designed for use as a trailing cable on AC mining equipment:
- Where service conditions are severe and maximum safety is mandatory (such as power shovels and draglines in open-pit mines, quarries,gantry cranes and slag reclaiming)
- For high-voltage distribution in underground mines where frequent relocation is necessary
Features:
• Simultaneous extrusion and vulcanization of both strand shield and insulation form a virtually perfect electrode, eliminating unequal electrical stresses
• Excellent heat, moisture, steam, oil, corona, chemical and radiation resistance
• Flexible for easy handling
• High dielectric strength
• Electrical stability under stress
• Low dielectric loss
• Resists cutting, impact, abrasion, flame and sunlight
• Excellent thermal stability and physical properties over a broad temperature range
• Two-layer jacket is reinforced to provide maximum protection from mechanical damage— the cause of most portable cable failures
Compliances:
• ICEA S-75-381 Portable and Power Feeder Cables for use in mines and similar applications
• Meets flame test requirements and is accepted for listing by MSHA
• Approved by the Pennsylvania Department of Environmental Protection
Packaging: Material cut to length and shipped on nonreturnable reels
technical specifications: | |
cond. size(awg/kcmil) | 4/0 |
no. of cond. | 3 |
cond. strand | 532 |
nominal insulation thickness(inches) | 0.210 |
nominal insulation thickness(mm) | 5.3 |
grd. cond. size(awg) | 1 |
grd-check cond. size(awg) | 8 |
nominal jacket thickness(inches) | 0.265 |
nominal jacket thickness(mm) | 6.7 |
nominal cable 0.d.(inches) | 3.05 |
nominal cable 0.d.(mm) | 77.5 |
copper weight(lbs/1000 ft) | 2973 |
copper weight(kg/km) | 4425 |
net weight(lbs/1000 ft) | 6860 |
net weight(kg/km) | 10209 |
ampacity | 325 |
catalog number | 16245.615400 |