General Cable Aluminum Uniblend® PVC 2/0 AWG High Speed Type MV-105 220 Mils EPR Copper Tape Shield PVC Shielded

General Cable Aluminum Uniblend® PVC 2/0 AWG High Speed Type MV-105 220 Mils EPR Copper Tape Shield PVC Shielded

Product Details

Conductor: 2 AWG thru 1000 kcmil 1350 aluminum compact Class B strand

Extruded Strand Shield (ESS): Extruded thermoset semi-conducting stresscontrol layer over conductor

Insulation: Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers

Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer free stripping from insulation

Metallic Shield: 5 mil annealed copper tape with an overlap of 25%

Jacket: Low-friction, lead-free, flame-retardant, moistureand sunlight-resistant Polyvinyl Chloride (PVC)

Options: STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610

Applications:
• Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications
• For use in wet or dry locations when installed in accordance with NEC
• For use in aerial, conduit, open tray and underground duct installations
• For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5)

Features:
• Rated at 105?C
• Low friction for easy pulling
• Excellent heat and moisture resistance
• Excellent flame resistance
• Outstanding corona resistance
• Flexibility for easy handling
• High dielectric strength
• Low moisture absorption
• Electrical stability under stress
• Low dielectric loss
• Chemical-resistant
• Meets cold bend test at -35?C
• 105°C rating for continuous operation
• 140°C rating for emergency overload conditions
• 250°C rating for short circuit conditions

Compliances:
• National Electrical Code (NEC)
• UL 1072
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• AEIC CS8
• UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501
• UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test
• Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC
• IEEE 1202 (70,000 BTU/hr)/CSA FT4 EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
• RoHS Compliant

Packaging:
• Material cut to length and shipped on nonreturnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit
• Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing

technical specification:
cond. size (awg/kcmil) 2/0
nominal conductor diameter(inches) 0.38
insulation diameter inches(min.) 0.820
insulation diameter inches(max.) 0.905
nominal jacket thickness(inches) 0.080
nominal jacket thickness(mm) 2.03
nominal cable(diameter in inches) 1.10
nominal cable(diameter in mm) 27.94
nominal cable(weight in lbs/1000ft) 652
nominal cable(weight in kg/km) 970
aluminum weight(lbs/1000ft) 125
aluminum weight(kg/km) 186
copper weight(lbs/1000ft) 81
copper weight(kg/km) 121
ampacity(conduit in air (1) in 90?c) 175
ampacity(conduit in air (1) in 105?c) 200
ampacity(underground duct (2) in 90?c) 175
ampacity(underground duct (2) in 105?c) 190
ampacity(tray (3) in 90?c) 175
ampacity(tray (3) in 105?c) 195
conduit sizing (4)(inches) 3.5
catalog number 17031.135208*

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question