Conductor: Soft annealed flexible stranded tinned copper per IEEE 1580
Insulation: GEXOL® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. 600V/IEC 1000V.
Jacket: A black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset compound meeting UL 1309/CSA 245 and IEEE 1580.
Safe to Handle: CIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors
Application: Designed and constructed to be a flexible alternative to Type MC cable where user desires crush and impact protection in arctic conditions.
Features:
• Complies with the requirements for TC-ER-HL per UL 2225*
• Exceeds CSA cold bend / cold impact (-40°C / -35°C)
• Gas & vapor tight – impervious to water & air
• Smaller bend radius (up to 40% smaller) than Type MC
• Reduced tray fill (up to 35% less) compared to Type MC
• Considerably more flexible than Type MC
• Reduced installation time and cost compared to Type MC
• Glands for this product cost up to 50% LESS than those for Type MC
technical specifications: | |
conductor size(awg) | 14 |
conductor size(mm2) | 2.1 |
number of conductors | 19 |
nominal diameter(inches) | 1.090 |
weight(lbs/1000 ft.) | 698 |
90°c nec ampacity | 12 |
75°c nec ampacity | 10 |
dc resistanceat 25°c(ohms/1000 ft.) | 3.00 |
ac resistanceat 90°c, 60hz(ohms/1000 ft.) | 3.75 |
voltage drop(volts/amp/1000 ft.) | 5.224 |
amercable part number | 37-102*-765CIRGAG |