General Cable EmPowr® 2 Inches CDC Underground Distribution Primary Combined Duct and Cable Primary Cable Installed in Polyethylene Duct

General Cable EmPowr® 2 Inches CDC Underground Distribution Primary Combined Duct and Cable Primary Cable Installed in Polyethylene Duct

Product Details

Complete Assembly: EmPowr® CDC® Combined Duct & Cable consists of insulated conductor factory installed in a black high-density polyethylene conduit. The polyethylene conduit is extruded directly over any prior-made single medium-voltage cable.

Complete Cable: All underground distribution cables in EmPowr CDC are manufactured and tested in accordance with applicable industry standards and/or individual customer specifications. See the appropriate catalog section for a complete cable description.

Conduit: The high-density polyethylene EPEC-A Conduit is manufactured and tested in accordance with NEMA Standard TC7, “Smooth-wall Coilable Electrical Polyethylene Conduit.”

Applications: EmPowr CDC Combined Duct & Cable offers an economical alternative to pulling cable in previously installed short lengths of duct joined with sleeve couplings. The inherent construction advantages and versatility of the EmPowr CDC design are ideally suited for underground primary distribution systems up to 46 kV.

Features and Benefits: In addition to the initial labor savings achieved from installation of cable and conduit in a single operation, cable replacement costs and ground disruption are significantly less for the EmPowr CDC cable system. Tough, yet light and flexible, high-density polyethylene conduit provides ease of installation and high impact resistance for cable protection.

Options:
• EPEC-B, EPEC-40 or EPEC-80 smooth-wall coilable electrical polyethylene conduit TC7
• Gray or red color
• Extruded red stripes

technical specifications:
nominal conduit size (inches) 2
minimum i.d. (inches) 2.033
o.d. (± 0.012") (inches) 2.375
minimum inside area (sq. inches) 3.246
approx. weight (lb/1000 ft) 475
minimum* wall thickness (inches) 0.145
minimum bend radius (inches) 26
minimum inside area (sq. inches) 3.246
maximum total cross-sectional area of conductors-53% fill one conductor (sq. inches) 1.720
minimum inside area (sq. inches) 2.033
maximum conductor diameter-one (1) conductor (inches) 1.480

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question