General Cable GenSPEED® 10,000 with 17 FREE Category 6A Cable Signal Strength and Power

General Cable GenSPEED® 10,000 with 17 FREE Category 6A Cable Signal Strength and Power

Select gauge from drop-down menu for prices:

General Cable GenSPEED® 10,000 with 17 FREE Category 6A Cable Signal Strength and Power

Product Details

Conductors: 23 AWG solid bare annealed copper 

Insulation: Non-Plenum: Polyolefin 

Color Code 
• Pair 1: Blue-White 
• Pair 2: Orange-White 
• Pair 3: Green-White 
• Pair 4: Brown-White 

Separator: T-Top cross-web 

Jacket: Non-Plenum: Zero-Halogen Polyolefin

Features and Benefits 
• No halogens 
• Less toxic 
• More environmentally friendly 
• Increased flexibility for easy installation 
• Performance guaranteed to 500 MHz 
• TRU-Mark® print legend contains footage markings from 1000’ to 0’ 
• Third-party verified for guaranteed performance 
• Extensive design development conducted to find the perfect blend of product performance and consistent manufacturability 
• Innovative T-Top cross-web provides superior internal electrical characteristics by locking the pairs into a systematic orientation within the cable 
• Superior flame and smoke characteristics achieved through innovative design and careful selection of materials with certified suppliers 
• AirEs jacket provides superior flexibility and maximum separation of pairs from cable to cable for consistent PSANEXT and PSAACRF performance 
• Made in U.S.A. 

Applications 
• IEEE 802.3: 10G BASE-T, 1000 BASE-T, 100 BASE-TX, 10 BASE-T, PoE, PoE+ 
• ANSI/TIA 854: 1000 BASE-TX 
• Digital Video 
• Broadband and Baseband Analog Video 
• CDDI, Token Ring, ATM Standard 

Compliances 
• ANSI/TIA 568-C.2 
• NEC/CEC Type CMR (UL 1666) for Non-Plenum 
• UL 444 
• RoHS Compliant Directive 2011/65/EU 
• ANSI/TIA 862 (Building Automation) 
• ICEA S-116-732 
• ISO/IEC 11801 Ed. 2.0 (Class EA) 
• IEC 60754-1 
• IEC 60754-2 
• IEC 61034-2

PHYSICAL DATA

cmr (non-plenum)
nominal cable diameter (in) 0.330
nominal cable weight (lbs/1000 ft) 48
minimum bend radius (in) 1.5
maximum pulling force (lbs) 40
temperature rating (?c)
installation:
operation:
-10 to +60
-20 to +75
PART NUMBERS
jacket color spool
cmr (non-plenum)
blue 7133819-17f
white 7133820-17f
yellow 7133822-17f
gray 7133821-17f
red 7133824-17f
orange 7133826-17f
green 7133823-17f
black 7133828-17f
pink 7133827-17f
purple 7133825-17f
ELECTRICAL PERFORMANCE
frequency
mhz
psacr*
(min)
acr*
(min)
insertion
loss(max)
psnext
(min)
next
(min)
psacrf
(min)
acrf
(min)
return loss
(min)
tcl
(min)
psanext
(min)
psaacrf
(min)
1 70.2 72.2 2.1 72.3 74.3 64.8 67.8 20.0 40.0 67.0 67.0
4 59.5 61.5 3.8 63.3 65.3 52.8 55.8 23.0 40.0 67.0 66.2
8 53.5 55.5 5.3 58.8 60.8 46.7 49.7 24.5 40.0 67.0 60.1
10 51.4 53.4 5.9 57.3 59.3 44.8 47.8 25.0 40.0 67.0 58.2
16 46.7 48.7 7.5 54.2 56.2 40.7 43.7 25.0 38.0 67.0 54.1
20 44.4 46.4 8.4 52.8 54.8 38.8 41.8 25.0 37.0 67.0 52.2
25 41.9 43.9 9.4 51.3 53.3 36.8 39.8 24.3 36.0 67.0 50.2
31.25 39.4 41.4 10.5 49.9 51.9 34.9 37.9 23.6 35.1 67.0 48.2
62.5 30.4 32.4 15.0 45.4 47.4 28.9 31.9 21.5 32.0 65.6 42.2
100 23.2 25.2 19.1 42.3 44.3 24.8 27.8 20.1 30.0 62.5 38.2
200 10.2 12.2 27.6 37.8 39.8 18.8 21.8 18.0 27.0 58.0 32.2
250 5.2 7.2 31.1 36.3 38.3 16.8 19.8 17.3 26.0 56.5 30.2
300 0.8 2.8 34.3 35.1 37.1 15.3 18.3 16.8 25.2 55.3 28.7
400 - - 40.1 33.3 35.3 12.8 15.8 15.9 24.0 53.5 26.2
500 - - 45.3 31.8 33.8 10.8 13.8 15.2 23.0 52.0 24.2
ELECTRICAL CHARACTERISTICS
max. nom.
dc resistance
ohms/100 m (328 ft) @ 20?c
9.38 7.50
dc resistance unbalance
individual pair %
4.00 < 1
delay skew
ns/100 m
45 30
nom. velocity of propagation
% speed of light
70
characteristic impedance
frequency (f): 1-500 mhz
ohms
100 ± 15