Helukabel 18 AWG 7 Cores JZ-750 Flexible Wire With Green-Yellow Conductor, Number Coded 750V Meter Marking Cable 10839

Helukabel 18 AWG 7 Cores JZ-750 Flexible Wire With Green-Yellow Conductor, Number Coded 750V Meter Marking Cable 10839

Select gauge from drop-down menu for prices:

Helukabel 18 AWG 7 Cores JZ-750 Flexible Wire With Green-Yellow Conductor, Number Coded 750V Meter Marking Cable 10839

Product Details

Technical data: 
• Special-PVC control cable adapted to DIN VDE 0285-525-2-51/ DIN EN 50525-2-51 

Temperature range: 
• Flexing -15°C to +80°C 
• Fixed installation -40°C to +80°C 

Nominal voltage: U0/U 450/750 V 

Test voltage: 4000 V 

Breakdown voltage: min. 8000 V 

Insulation resistance:
• min. 20 MOhm x km 

Minimum bending radius: 
• Flexing 7,5x cable Ø 
• Fixed installation 4x cable Ø 

Radiation resistance: 
• Up to 80x106 cJ/kg (up to 80 Mrad) 

Cable structure: 
• Bare copper-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5 
• Core insulation of special PVC compound type TI2 to DIN VDE 0207-363-3/DIN EN 50363-3 
• Core identification to DIN VDE 0293 black cores with continuous white numbering 
• GN-YE conductor, 3 cores and above in the outer layer 
• Cores stranded in layers with optimal lay-length 
• Outer sheath of special PVC compound type TM2 to DIN VDE 0207-363-4-1/DIN EN 50363-4-1 
• Sheath colour grey (RAL 7001)  
• With meter marking 

Properties: 
• Extensively oil resistant, oil-/chemical resistance see table Technical Informations 
• The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers 

Tests: 
• PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B) 

Note: 
• G = with green-yellow conductor x = without green-yellow conductor (OZ) 
• Cleanroom qualification tested with analog type. Please note "cleanroom qualified" when ordering. 
• AWG sizes are approximate equivalent values. The actual cross-section is in mm². 

Application: 
These cables are used for flexible use for medium mechanical stresses with free movement without tensile stress or forced movements in dry, moist and wet rooms but not suitable for open air, wherever internationally recognized PVC cables are required. E. g. as a control or measurements cable on industrial machinery, on conveyor systems or in industrial plants, etc. The number coding has been brought onto the cores in such a way that it is easily identifiable and the core numbers are individually underlined to avoid confusion. The green-yellow earth core is laid in the outer layer. = The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

technical specification:
awg-no. 18
no.cores x cross-sec. mm² 7 G 1
outer ø app. mm 9,5
cop. weight kg/km 68,0
weight app. kg/km 186,0
helukabel part number 10839