HW268 THREE CONDUCTOR POWER CABLE 0.6/1kV Armored 110°C Gexol® Insulation - 1/0 AWG

HW268 THREE CONDUCTOR POWER CABLE 0.6/1kV Armored 110°C Gexol® Insulation - 1/0 AWG

Select gauge from drop-down menu for prices:

HW268 THREE CONDUCTOR POWER CABLE 0.6/1kV Armored 110°C Gexol® Insulation - 1/0 AWG
HW268 THREE CONDUCTOR POWER CABLE 0.6/1kV Armored 110°C Gexol® Insulation - 1/0 AWG
Technical Specifications:
Catalog Number HW268 10103
Size AWG 1/0
mm2
54
Nominal Diameter (inches) 1.376
Weight (lbs/Mft.) 1781
DC Resistance at 25° C (Ohms/1000 ft.)
0.117
AC Resistance at 110°C, 60 Hz (Ohms/1000 ft.) 0.156
Inductive Reactance (Ohms/1000 ft.) 0.028
Voltage Drop at 110°C (Volts/Amp/1000 ft.) 0.245
Opt. Uninsulated Grounding Cond. Size AWG 1
6
Ampacity 110°C 176
Ampacity 100°C
164
Ampacity 95°C 152

Specifications:

  • HW268
  • THREE CONDUCTOR
  • POWER CABLE
  • 0.6/1kV Unarmored 110°C
  • Gexol® Insulation
  • Made in the USA

Application:
Designed and constructed for the demanding environments of offshore drilling and petroleum facilities located throughout the world.

Conductors:
Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.

Insulation/Jacket:
Flame Retardant Cross-linked Polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA C22.2 No. 245. Color Code: Black-White-Red. (Black-White-Green on request) Sizes 1/0 and Larger: Black with Phase ID Imprint.

Jacket:
Black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA C22.2 No. 245 and IEEE 1580.

Ratings & Approvals :

  • American Bureau of Shipping (ABS)
  • Transport Canada
  • Det Norske Veritas (DNV)
  • Lloyd's Register of Shipping (LRS)
  • NVE 95/1696, FAL
  • UL listed as Marine Shipboard Cable
  • United States Coast Guard
  • CSA listed as Marine Shipboard Cable

Features:

  • High strand count conductors make this product extremely flexible, easier to install and more resistant to vibration than Type MC, IEC spec or commercial cables.
  • Lower dielectric constant and higher insulation resistance reduces electrical losses.
  • Excellent resistance to moisture produces stable electrical properties throughout the life of the cable.
  • In fire conditions, non chlorinated flame retardant system produces less toxic and less corrosive gasses.
  • Dual certified IEEE 1580 Type P and UL 1309/CSA C22.2 No. 245 Type X110.
  • Highest ampacity ratings: ABS 100°C, DNV 95°C, LRS 95°C, Transport Canada 95°C
  • Severe cold durability: exceeds CSA cold bend/cold impact (-40/-35° C)
  • Flame retardant: IEC 60332-3 Category A and IEEE 1202