Power Cable 2.4KV UL Type MV-105 2/0
Select gauge from drop-down menu for prices:
- Power Cable 2.4KV UL Type MV-105, 105°C Three Conductor, Non-Shielded EPR Insulation, PVC Jacket 2.4KV 133% Insualtion Level Copper Conductor
- Power Cable 2.4KV UL Type MV-105 6 Gauge
- Power Cable 2.4KV UL Type MV-105 4 Gauge
- Power Cable 2.4KV UL Type MV-105 2 Gauge
- Power Cable 2.4KV UL Type MV-105 1 Gauge
- Power Cable 2.4KV UL Type MV-105 1/0
- Power Cable 2.4KV UL Type MV-105 3/0
- Power Cable 2.4KV UL Type MV-105 4/0
- Power Cable 2.4KV UL Type MV-105 250 MCM
- Power Cable 2.4KV UL Type MV-105 350 MCM
- Power Cable 2.4KV UL Type MV-105 500 MCM
- Power Cable 2.4KV UL Type MV-105 750 MCM
Technical Specifications: | |
Size (AWG or kcmil): | 2/0 |
No. of Strands | 19 |
Insulation Thickness (Mils): | 115 |
Jacket Thickness (Mils): | 80 |
Insulation Diameter (Inch): | 0.68 |
Explosion Proof Connector UN | 424UN07 |
Copper Grounding Conductor AWG | 4 |
Overall Diameter (Inch): | 1.66 |
Net Weight (Lbs.): | 2150 |
Specifications:
- HW212 Power Cable
- 2.4KV UL Type MV-105, 105°C
- Three Conductor, Non-Shielded
- EPR Insulation, PVC Jacket
- 2.4KV 133% Insualtion Level
- Copper Conductors
Application:
For use in primary power and distribution circuits up to 2.4kv when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA standards.
Grounding Conductor:
Compressed soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance to UL Standard 1072.
Jacket:
Sunlight-resistant PVC per ICEA Standards and UL Standard 1072.
Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger.
Color Code:
ICEA Method 4
Additional Standards:
- ICEA S-96-659
- NEMA WC71
Connectors:
Explosion Proof, Class I, Division 2: 424UN series – aluminum exterior components, nickel-plated brass interior components.
Note:
CT rating must be requested. CT ratings are available on all sizes.