Technical Specifications: | |
Size (AWG or kcmil): | 4 |
No. of Strands | 7 |
Insulation Thickness (Mils): | 115 |
Jacket Thickness (Mils): | 80 |
Insulation Diameter (Inch): | 0.52 |
Explosion Proof Connector UN | 424UN06 |
Copper Grounding Conductor AWG | 6 |
Overall Diameter (Inch): | 1.48 |
Net Weight (Lbs.): | 1265 |
Specifications:
- HW213 Power Cable
- 5KV/8KV UL Type MV-105, 105°C
- Three Conductor, Shielded
- EPR Insulation, PVC Jacket
- 5KV 133%, 8KV 100% Insulation Level
- Copper Conductors
Application:
For use in primary power and distribution circuits up to 8KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682 with a semi-conducting insulation shield.
Shield:
Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.
Grounding Conductor:
Compressed soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance to UL Standard 1072.
Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.
Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger.
Color Code:
ICEA Method 4
Additional Standards:
- ICEA S-93-639
- NEMA WC74
- AEIC CS8
- Federal Specification J-C-30B
Connectors:
Explosion Proof, Class I, Division 2: 424UN series – aluminum exterior components, nickel-plated brass interior components.
Note:
CT rating must be requested. CT ratings are available on all sizes.