Technical Specifications: | |
Size (AWG or kcmil): | 6 |
No. of Strands | 7 |
Net Weight: | 260 |
Overall Diameter (Inches): | 0.65 |
Insulation Thickness (Mils): | 125 |
Jacket Thickness (Mils): | 80 |
Specifications:
- HW201
- Power Cable
- 2.4KV UL Type MV-90, 90°C
- Single Conductor, Non-Shielded
- EPR Insulation, Hypalon® Jacket - Heavy Wall
- 2.4KV 133% Insulation Level
- Copper Conductor
Application:
For use in caustic environments in power circuits up to 2.4kv when installed in open air, conduit, duct, cable tray when CT rated, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA standards.
Jacket:
Chlorosulfonated polyethylene (CSPE/Hypalon®) per ICEA standards.
Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test – for CT-listed sizes 1/0 AWG and larger.
Additional Standards:
- ICEA S-96-659
- UL Standard 1072
- NEMA WC71
Note:
- CT rating must be requested. CT ratings are available on sizes 1/0 AWG and larger.
- PVC jacket available upon request.