Conductors: Soft annealed stranded tinned copper per ASTM B 33. A polyester tape separator is used over the conductor.

Insulation: Bostrig Type P chemically cross-linked polyolefin (XLPO), meeting IEEE 1580.

Jacket: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option.

Armor: Braided bronze in accordance with IEEE 1580.

Sheath: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) applied over the armor in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option.

Applications:
Bostrig™ Type P Marine and Offshore Cable is primarily designed for power, control, signal, and instrumentation applications for offshore and land drilling rigs, marine vessels, and offshore production facilities. Bostrig™ cables have excellent resistance to oil, abrasion, moisture, vibration, sunlight, and ester based mud (Type P- MR). They are suitable for use in Class 1, Division 1 offshore applications (armored & sheathed). The standard insulation has a continuous operating temperature of 125°C, allowing for higher ampacity levels. These cables also meet cold bend requirements of -40°C and cold impact of -35°C (CSA 22.2 N0. 0.3). This product may be manufactured in an unarmored or armored and sheathed version.

Features/Ratings:
• Superior resistance to oil, abrasion, moisture, sunlight, crush and impact
• High strand count conductors provide superior flexibility
• Higher allowable conductor operating temperature results in increased ampacity
• Cold bend/ cold impact of -40°/ -35°C in accordance with CSA 22.2 No. 0.3
• Flame retardant in accordance with IEEE 1202 and IEC 60332-3-22 Category A
• Meets IEEE standards for 600V and performance requirements of IEC standards for 0.6/1 kV
• Armored and sheathed cables suitable for use in Class 1 Division 1 and Zone 1 hazardous locations offshore

Approvals:
• IEEE 1580 and IEEE 45- Marine Shipboard Cable
• UL 1309- Marine Shipboard Cable Type X110
• CSA 22.2 No. 245- Marine Shipboard Cable Type X110
• Det Norske Veritas (DNV)
• American Bureau of Shipping (ABS)
• Transport Canada Approved AMS400-20-2
• Transport Canada 8700-20-2
• Lloyd’s Register of Shipping (LRS)
• United States Coast Guard-46CFR

Technical Specification
Conductor Size (AWG/MCM) 3
Conductor Size (mm2) 25.6
Type Designation FPNBS-3
Sheath Thickness (in)
0.080
Sheath Thickness(mm2) 2.0
Cable Diameter (nominal) (in) 1.340
Cable Diameter (nominal) (mm2) 34.0
Impedance (phase-neutral) (ω/kft) 0.23
Impedance (phase-neutral) (ω/km) 0.8
Inductance (mh/kft) 0.11
Inductance (mh/km) 0.4
Capacitance (pf/ft) 173
Capacitance (pf/m) 567
Calculated Ampacity (measured @ ºc) (95) 99
Calculated Ampacity (measured @ ºc) (100) 108
Calculated Ampacity (measured @ ºc) (110) 116
Calculated Ampacity (measured @ ºc) (125*) 148
Cable Weight (approximate) (Lbs/mft) 1,525
Cable Weight (approximate) (kg/km) 2,270