Prysmian and Draka Cable 313 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26120
Select gauge from drop-down menu for prices:
- Prysmian and Draka Cable 8 AWG to 777 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable
- Prysmian and Draka Cable 8 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26108
- Prysmian and Draka Cable 6 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26109
- Prysmian and Draka Cable 5 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26110
- Prysmian and Draka Cable 4 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26111
- Prysmian and Draka Cable 3 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26112
- Prysmian and Draka Cable 2 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26113
- Prysmian and Draka Cable 1 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26114
- Prysmian and Draka Cable 1/0 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26115
- Prysmian and Draka Cable 2/0 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26116
- Prysmian and Draka Cable 3/0 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26117
- Prysmian and Draka Cable 4/0 AWG Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26118
- Prysmian and Draka Cable 262 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26119
- Prysmian and Draka Cable 373 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26121
- Prysmian and Draka Cable 444 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26122
- Prysmian and Draka Cable 535 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26123
- Prysmian and Draka Cable 646 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26124
- Prysmian and Draka Cable 777 MCM Bostrig Type P Two Conductor Armored and Sheathed 600V Power Cable T26125
Conductors: Soft annealed stranded tinned copper per ASTM B 33. A polyester tape separator is used over the conductor.
Insulation: Bostrig Type P chemically cross-linked polyolefin (XLPO), meeting IEEE 1580.
Jacket: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option.
Armor: Braided bronze in accordance with IEEE 1580.
Sheath: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) applied over the armor in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option.
Applications:
• Bostrig™ Type P Marine and Offshore Cable is primarily
designed for power, control, signal, and instrumentation
applications for offshore and land drilling rigs, marine
vessels, and offshore production facilities.
• Bostrig™ cables have excellent resistance to oil, abrasion,
moisture, vibration, sunlight, and ester based mud
(Type P- MR). They are suitable for use in Class 1,
Division 1 offshore applications (armored and sheathed).
• The standard insulation has a continuous operating
temperature of 125°C, allowing for higher ampacity levels.
These cables also meet cold bend requirements of -40°C
and cold impact of -35°C (CSA 22.2 N0. 0.3).
• This product may be manufactured in an unarmored
or armored and sheathed version.
Features and Ratings:
• Superior resistance to oil, abrasion, moisture,
sunlight, crush and impact
• High strand count conductors provide superior
flexibility
• Higher allowable conductor operating temperature
results in increased ampacity
• Cold bend/ cold impact of -40°/ -35°C in accordance
with CSA 22.2 No. 0.3
• Flame retardant in accordance with IEEE 1202 and
IEC 60332-3-22 Category A
• Meets IEEE standards for 600V and performance
requirements of IEC standards for 0.6/1 kV
• Armored and sheathed cables suitable for use in
Class 1 Division 1 and Zone 1 hazardous locations
offshore
Approvals:
• IEEE 1580 and IEEE 45- Marine Shipboard Cable
• UL 1309- Marine Shipboard Cable Type X110
• CSA 22.2 No. 245- Marine Shipboard Cable Type X110
• Det Norske Veritas (DNV)
• American Bureau of Shipping (ABS)
• Transport Canada Approved AMS400-20-2
• Transport Canada 8700-20-2
• Lloyd’s Register of Shipping (LRS)
• United States Coast Guard-46CFR
technical specification: | |
conductor size(awg/mcm) | 313 |
conductor size(mm2) | 158.6 |
sheath thickness (in) | 0.110 |
sheath thickness (mm) | 2.8 |
cable diameter (nominal) - (in) | 2.250 |
cable diameter (nominal) - (mm) | 57.2 |
impedance (phase-neutral) - (ω/kft) | 0.05 |
impedance (phase-neutral) - (ω/km) | 0.1 |
inductance (mh/kft) | 0.09 |
inductance (mh/km) | 0.3 |
capacitance (pf/ft) | 270 |
capacitance (pf/m) | 886 |
calculated ampacity† (measured @ 90ºc) | 362 |
calculated ampacity† (measured @ 100ºc) | 391 |
calculated ampacity† (measured @ 110ºc) | 419 |
calculated ampacity† (measured @ 125ºc) | 539 |
cable weight (approximate) - (lbs/mft) | 4,005 |
cable weight (approximate) - (kg/km) | 5,960 |
type designation | dpnbs-313 |
prysmian and draka cable part number | T26120 |