Product Details
Conductors: Class I flexible stranded, tinned copper confirming to ASTM B-33 and UL requirements.
Insulation & Covering: Heat and moisture resistant, low smoke, non-halogen, composite Insulation with a natural cotton braid conforming to UL Standard 44, Telcordia Specification GR-347-CORE and ATIS Specification 0600017.2009.
Surface Marking: "PRYSMIAN ECOSAFE ®-CO IV ™ CABLE-T (YEAR) PN [part number] # [conductor size or kcmil] CU NONHALOGEN RHW-2 600V FT4 ST1 Oil Res SR *CT VM1 (on sizes 1/0 AWG and larger) or AWM STYLE 3578 I A/B 105C “YEAR SEQUENTIAL FOOTAGE MARKS". Sequential footage markings shall be applied at 2 foot intervals"
Applications: Central Office Power Cable, Class I flexible tinned copper strand with braid. The cable has a low smoke, zero halogen, lead-free and silicone free composite insulation.Central Office Power Cable is 105°C dry, 90°C wet. UL Listed RHW-2/USE-2, FT4 / ST1, 90°C wet/dry, 600 volts. Sizes 1/0 and larger are UL CT Use rated.
Specifications:
• UL Listed Standard 509, Central Office
• UL Listed Standard 44 Type RHW-2 FT4/ST1 (Low Smoke) VW-1 For CT USE (1/0 AWG & Larger) Oil Resistance II Sunlight Resistant
• ASTM B-33 & B-172-Flexible Strand
• GR-347-Core Compliant by Telcordia
• ATIS 0600017.2009 Compliant
• Low Smoke, Zero Halogen (LSZH)
technical specification | |
size(awg/kcmil) | 4/0 |
stranding | 532 |
insulation min. avg. wall | 80 |
nominal insulation diameter (in) | 0.75 |
nominal overall diameter (in) | .784 |
max dc res @ 20°c (ohms/ mft) | 0.055 |
approximate weight (lb/mft) | 819 |
list | list 4 |
prysmian and draka cable part number | 088910 |