Prysmian Cable 1000 MCM 35kV EPR URD 133% Copper Three Phase One Third Neutral Medium Voltage Utility Cables QRG0001A

Prysmian Cable 1000 MCM 35kV EPR URD 133% Copper Three Phase One Third Neutral Medium Voltage Utility Cables QRG0001A

Select gauge from drop-down menu for prices:

Prysmian Cable 1000 MCM 35kV EPR URD 133% Copper Three Phase One Third Neutral Medium Voltage Utility Cables QRG0001A
Prysmian Cable 1000 MCM 35kV EPR URD 133% Copper Three Phase One Third Neutral Medium Voltage Utility Cables QRG0001A

Conductors: Solid or Class B Compressed concentric strand Aluminum alloy 1350 or soft drawn annealed copper per ASTM. 

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation. 

Insulation: Natural high dielectric strength EPROTENAX™ EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life. 

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping. 

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.  

Jacket: Black, insulating, sunlight resistant, linear low density polyethylene encapsulating the neutral wires with three extruded red stripes and NESC lightning bolt symbol. 

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket. 

Options: 
• Black LLDPE jacket with no stripes 
• Black PVC jacket sleeved over separator tape 
• No Jacket 
• Multiplex cables 
• Tinned round and flat strap neutrals 
• Strandseal® 
• Compact stranded conductors 
• UL MV-90 Rating if required 
• 46kV 
• RUS - Bulletin 1728F-U1 

Installation: 
• Conduit in Air 
• Underground Duct 
• Wet Locations 
• With Messenger 
• Direct Buried 
• Isolated in Air 
• Dry Locations 
• Utility Primary 

Specifications and ratings: 
• AEIC- AEIC CS8 
• ICEA- ICEA S-94-649 
• For 105°C continuous, 140°C emergency, 250°C short-circuit operation.

technical specification:
conductor 1000 MCM CU
insulation thickness (mils) 420
concentric neutral 21-#8
conductor diameter (in) - (a) 1.124
insulation diameter (in) - (b) 2.03
insulation shield diameter (in) - (c) 2.15
jacket diameter (in) - (d) 2.58
cable weight (lbs/kft) 6073
minimum bending radius (in) 21
† ampacity (amps) - 105°c in duct 671
+/- sequence impedance resistance (µΩ/ft) - 105°c in duct 23
+/- sequence impedance reactance (µΩ/ft) - 105°c in duct 36
zero sequence impedance resistance (µΩ/ft)†† - 105°c in duct 56
zero sequence impedance reactance (µΩ/ft)†† - 105°c in duct
20
† ampacity (amps) - 90°c direct buried 682
+/- sequence impedance resistance (µΩ/ft) - 105°c direct buried 39
+/- sequence impedance reactance (µΩ/ft) - 105°c direct buried 40
zero sequence impedance resistance (µΩ/ft)†† - 105°c direct buried 55
zero sequence impedance reactance (µΩ/ft)††- 105°c direct buried 20
prysmian cable part number QRG0001A