Prysmian Cable 750 MCM 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAX00ZC
Select gauge from drop-down menu for prices:
- Prysmian Cable 25kV 133% Aluminum TRXLPE URD CSA Medium Voltage Utility Cables
- Prysmian Cable 1 Solid 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAN01ZC
- Prysmian Cable 1 AWG 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAO01ZC
- Prysmian Cable 1/0 Solid 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAP01ZC
- Prysmian Cable 1/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAQ01ZC
- Prysmian Cable 2/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAR01ZC
- Prysmian Cable 3/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAS01ZC
- Prysmian Cable 4/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAT01ZC
- Prysmian Cable 250 MCM 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAU01ZC
- Prysmian Cable 350 MCM 25kV 133% Aluminum TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables QAV01ZC
- Prysmian Cable 1 Solid 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAN00ZC
- Prysmian Cable 1 AWG 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAO00ZC
- Prysmian Cable 1/0 Solid 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAP00ZC
- Prysmian Cable 1/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAQ00ZC
- Prysmian Cable 2/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAR00ZC
- Prysmian Cable 3/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAS00ZC
- Prysmian Cable 4/0 AWG 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAT00ZC
- Prysmian Cable 250 MCM 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAU00ZC
- Prysmian Cable 350 MCM 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAV00ZC
- Prysmian Cable 500 MCM 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAW00ZC
- Prysmian Cable 1000 MCM 25kV 133% Aluminum TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables QAY00ZC
Conductor: Solid or Class B compact or compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.
Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes.
Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.
Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• EPROTENAX™ (EPR) insulation
• Multiplex cables
• Tinned round and flat strap neutrals
• Strandseal®
• Super smooth conductor shield
• Cables made to AEIC CS8 and/or ICEA S-94-649
• 46kV
Installations:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary
Specifications and Ratings:
• CSA - CSA C68.5 -40°C
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.
technical specifications: | |
conductor | 750 MCM al |
insulation thickness (mils) | 320 |
concentric neutral | 24-#12 |
conductor diameter (in) - (a) | 23.11 |
insulation diameter (in) - (b) | 41.30 |
insulation shield diameter (in) - (c) | 44.50 |
jacket diameter (in) - (d) | 52.87 |
cable weight (lbs/kft) | 3436 |
minimum bending radius (in) | 432 |
† ampacity (amps) - 90°c in duct | 476 |
+/- sequence impedance resistance (µΩ/ft) - 90°c in duct | 0.11 |
+/- sequence impedance reactance (µΩ/ft) - 90°c in duct | 0.13 |
zero sequence impedance resistance (µΩ/ft)†† - 90°c in duct | 0.39 |
zero sequence impedance reactance (µΩ/ft)†† - 90°c in duct | 0.07 |
† ampacity (amps) - 90°c direct buried | 517 |
+/- sequence impedance resistance (µΩ/ft) - 90°c direct buried | 0.18 |
+/- sequence impedance reactance (µΩ/ft) - 90°c direct buried | 0.19 |
zero sequence impedance resistance (µΩ/ft)†† - 90°c direct buried | 0.39 |
zero sequence impedance reactance (µΩ/ft)††- 90°c direct buried | 0.07 |
prysmian cable part number | QAX00ZC |