Superior Essex Cable 4/0 AWG u2153 Reduced Neutral EPR/CN/LLDPE MV-90 Type Primary UD Copper Conductors Unfilled 35KV Cable E9MPT-4A1B01CA00

Superior Essex Cable 4/0 AWG ⅓ Reduced Neutral EPR/CN/LLDPE MV-90 Type Primary UD Copper Conductors Unfilled 35KV Cable E9MPT-4A1B01CA00

Select gauge from drop-down menu for prices:

Superior Essex Cable 4/0 AWG ⅓ Reduced Neutral EPR/CN/LLDPE MV-90 Type Primary UD Copper Conductors Unfilled 35KV Cable E9MPT-4A1B01CA00
Superior Essex Cable 4/0 AWG ? Reduced Neutral EPR/CN/LLDPE MV-90 Type Primary UD Copper Conductors Unfilled 35KV Cable E9MPT-4A1B01CA00

The Medium Voltage Primary Underground Distribution (UD) cables consist of a Copper (filled or unfilled) conductor, covered with ethylene propylene rubber (EPR), a concentric neutral of helically applied copper wires, and a linear low-density polyethylene (LLDPE) jacket with 3 extruded red stripes.

Features:
• High dielectric strength
• Low moisture absorption
• Low dielectric loss
• Excellent resistance to treeing
• Jacket is sunlight-resistant
• Designed to operate continuously at a conductor temperature not exceeding
•105°C for normal operations
• 140°C for emergency overload
• 250°C for short circuit

Specifications:
Conductor Count: 1 conductor

Conductor: Fully annealed bare copper Class B compressed strand (filled or unfilled)

Gauge Sizes: 
• Filled: Available in 2 AWG through 1000 kcmil
• Unfilled: Available in 2 AWG through 1000 kcmil

Conductor Strand Shield: Extruded thermoset Super-Smooth semi-conducting polymer over the conductor

Insulation: Ethylene Propylene Rubber (EPR)

Insulation Shield: Extruded thermoset semi-conducting polymer over the insulation

Neutral: Helically applied, annealed, solid bare copper wires

Jacket: Linear Low-Density Polyethylene (LLDPE)

Jacket Marking: 00000 FT SUPERIOR ESSEX XXAWG (KCMIL) AL or CU 1/C XXKV XXX% INSUL LEVEL XXXMILS EPR AA X #BB LLDPE JKT MV-90 (UL) MADE IN USA MMDDYYYY

Packaging: Non-returnable wood reels in a variety of lengths and dimensions

Performance Compliances: 
•ASTM B-3
• ICEA S-94-649
• ICEA T-31-610 (water block compliance)
• AEIC CS8
• UL 1072 (MV-90)
• RUS U1

Applications:
• Suitable for underground primary power applications
• For wet or dry locations
• For direct burial or in duct

Note:
Also Available in:
• Copper Unfilled, 15kV 133% I.L., 175-mils
• Copper Filled, 15kV 133% I.L., 175-mils

technical specification:
conductor size awg/kcmil 4/0
nominal conductor diameter¹ in (mm)
0.507 (12.9)
nominal insulation diameter¹ in (mm) 1.26 (32.0)
concentric neutral no. x awg 18 x 14
nominal jacket thickness¹ in (mm)
0.055 (1.40)
nominal overall diameter¹ in (mm) 1.58 (40.1)
nominal net weight¹ lbs/kft (kg/km) 1,697 (2,529)
ampacity (underground duct) 342
ampacity (direct buried²) 415
superior essex cable part number E9MPT-4A1B01CA00