Product Details
Conductor:
• Bare annealed copper per ASTM B3
• Class B stranding per ASTM B8
Insulation:
• Cross-Linked Polyethylene (XLPE) insulation per ICEA S-73-532 and UL 44, Listed XHHW-2
• Color-coded per ICEA Method 1, Table E2, full-colored insulation with stripes • Color-coded per CSA C22.2 No. 123 where applicable
Cable Assembly:
• Insulated conductors are cabled together with non-hygroscopic fillers when required
• A binder tape, when required, is applied over the cabled core
CCW Armor:
• Impervious, continuously welded and corrugated aluminum alloy sheath per UL 1569
• CCW armor conductivity meets the grounding requirements of NEC Article 250
Jacket:
• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
• Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C '• Meets CSA Low Acid Gas requirements
Applications:
• CCW armored Control cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods
• For use in Class I and II, Division 2; Class III, Divisions 1 and 2; and Class I, Zone 2 hazardous locations per NEC Articles 501, 502, 503 and 505
• For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC Articles 330 and 725
• Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial cable on a messenger, in cable trays, or as exposed runs secured to supports in accordance with NEC Article 330
• Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
Features:
• CCW armor provides an impervious barrier to moisture, gas and liquids
• CCW armor provides EMI shielding performance
• Factory assembled and tested cable for use as an alternative to cable in conduit wiring systems
• Meets cold impact at -40°C
• 90°C continuous operating temperature, wet or dry
• 130°C emergency rating
• 250°C short circuit rating
Specifications:
Design Adherence:
• ICEA S-73-532/WC-57 Standard for Control, Thermocouple Extension and Instrumentation Cables
• UL 44 Rubber Insulated Wires and Cables
• UL 1569 Metal Clad Cables
• UL 1309 Marine Shipboard Cable
• CSA C22.2 No. 123 Metal Sheathed Cables
Flame Tests:
• ICEA T-29-520 (210,000 BTU/hr)
• IEEE 383 (70,000 BTU/hr)
• CSA FT4
• IEEE 1202 (70,000 BTU/hr)
• UL 1581 (70,000 BTU/hr)
• IEC 60332-3 Cat. A
Compliances:
• UL Type MC, XHHW-2, SUN RES, CT USE, DIR BUR, -40°C, UL File # E69797
• UL Listed Marine Shipboard, UL File # E85994
• American Bureau of Shipping (ABS) Listed for CWCMC
• CSA certified1 Type RA90, XLPE, HL, SR, FT4, and -40°C, CSA File # 7319
• RoHS Compliant
technical specification: | |
cond. size (awg) | 12 |
no. of cond. | 7 |
insulation thickness (mils) | 30 |
insulation thickness (mm) | 0.76 |
nominal core o.d. (inches) | 0.47 |
nominal core o.d. (mm) | 11.9 |
nominal armor o.d. (inches) | 0.67 |
nominal armor o.d. (mm) | 17.0 |
jacket thickness (mils) | 50 |
jacket thickness (mm)
|
1.27 |
nominal overall o.d. (inches) | 0.78 |
nominal overall o.d. (mm) | 19.8 |
crosssectional area¹(sq. in.) | 0.48 |
approximate net weight (lbs/1000 ft)
|
328 |
approximate net weight (kg/1000 m) | 489 |
90°c ampacity @ 30°c ambient² | 20 |
catalog number | 9525.01207000 |