Eutex Cable 14 Pairs 0.75 Nominal Area BU (I) S13 Fire Resistant Instrumentation Cable with Individual Screen 250V

Eutex Cable 14 Pairs 0.75 Nominal Area BU (I) S13 Fire Resistant Instrumentation Cable with Individual Screen 250V

Select gauge from drop-down menu for prices:

Eutex Cable 14 Pairs 0.75 Nominal Area BU (I) S13 Fire Resistant Instrumentation Cable with Individual Screen 250V
Eutex Cable 14 Pairs 0.75 Nominal Area BU (I) S13 Fire Resistant Instrumentation Cable with Individual Screen 250V

Conductor: Stranded tinned annealed copper wires as per IEC 60228, Class 2 

Fire Resisting Layer: Mica/glass tape

Insulation: HF EPR as per IEC 60092-351

Twisting: Two/Three Insulated cores shall be twisted together to form a pair/triad

Individual Screen:
• Screened by copper or aluminium backed polyester tape with tinned copper drain wire.
• Each pair/triad is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triads.

Cabling:
• Screened pairs/triads shall be cabled.
• Flame retardant & non-hygroscopic fillers may be used.
• Suitable tape(s) may be applied on the cabled core.

Sheath:
• SHF2 or SHF MUD as per IEC 60092-359
• Outer sheath color: Grey
• Any other color scheme may be applicable when purchaser required.

technical specification
no. of pairs 14 P
conductor nominal area(sqmm) 0.75
conductor max. dia. of wires(mm) 7
conductor max. overall dia.(mm) 1.2
thickness of insulation(mm) 0.6
thickness of sheath(mm) 1.7
overall diameter nominal(mm) 23.2
overall diameter tolerance(±mm) 1.0
conductor resistance (at 20°c) (max.)(Ω/km) 26.3
insulation resistance (at 20°c) (min.)(ΜΩ-km) 1,170
test voltage (v/5min.) 1,500
cable weight approx.(kg/km) 800
application standard
design guide IEC 60092-350 & IEC 60092-376
insulation material IEC 60092-351, HF EPR
sheath material IEC 60092-359, SHF2
flame retardant IEC 60332-1 & IEC 60332-3 Category A
fire resistance IEC 600331-21 or -31
halogen content IEC 60754-1, 0.5%↓
smoke emission IEC 61034, 60%↑
fluorine content IEC 60684-2, 0.1%↓
ph and conductivity IEC 60754-2, pH 4.3%↑ & conductivity 10 μS/mm↓
cold bend/impact CSA 22.2 NO. 0.3(-40°C/-34°C)
mud resistant NEK 606 (Mud type only)
sunlight(uv) resistant UL 1581
max. rated conductor temperature 90°c

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question