Conductor: Stranded tinned annealed copper wires as per IEC 60228, Class 2 

Fire Resisting Layer: Mica/glass tape

Insulation: HF EPR as per IEC 60092-351

Twisting: Two/Three Insulated cores shall be twisted together to form a pair/triad

Individual Screen:
• Screened by copper or aluminium backed polyester tape with tinned copper drain wire.
• Each pair/triad is wrapped with polyester tape to prevent electrical contact with adjacent pairs/triads.

Cabling:
• Screened pairs/triads shall be cabled.
• Flame retardant & non-hygroscopic fillers may be used.
• Suitable tape(s) may be applied on the cabled core.

Sheath:
• SHF2 or SHF MUD as per IEC 60092-359
• Outer sheath color: Grey
• Any other color scheme may be applicable when purchaser required.

technical specification
no. of pairs 4 P
conductor nominal area(sqmm) 0.75
conductor max. dia. of wires(mm) 7
conductor max. overall dia.(mm) 1.2
thickness of insulation(mm) 0.6
thickness of sheath(mm) 1.3
overall diameter nominal(mm) 14.5
overall diameter tolerance(±mm) 0.7
conductor resistance (at 20°c) (max.)(Ω/km) 26.3
insulation resistance (at 20°c) (min.)(ΜΩ-km) 1,170
test voltage (v/5min.) 1,500
cable weight approx.(kg/km) 290
application standard
design guide IEC 60092-350 & IEC 60092-376
insulation material IEC 60092-351, HF EPR
sheath material IEC 60092-359, SHF2
flame retardant IEC 60332-1 & IEC 60332-3 Category A
fire resistance IEC 600331-21 or -31
halogen content IEC 60754-1, 0.5%↓
smoke emission IEC 61034, 60%↑
fluorine content IEC 60684-2, 0.1%↓
ph and conductivity IEC 60754-2, pH 4.3%↑ & conductivity 10 μS/mm↓
cold bend/impact CSA 22.2 NO. 0.3(-40°C/-34°C)
mud resistant NEK 606 (Mud type only)
sunlight(uv) resistant UL 1581
max. rated conductor temperature 90°c