Prysmian and Draka Cable 2 Cores 2.5 Cross-section core RU 0.6/1kV Unarmoured Power Cable 840301

Prysmian and Draka Cable 2 Cores 2.5 Cross-section core RU 0.6/1kV Unarmoured Power Cable 840301

Prysmian and Draka Cable 2 Cores 2.5 Cross-section core RU 0.6/1kV Unarmoured Power Cable 840301

Conductor: Tinned stranded circular copper, BS6360, class 2

Insulation: EP-rubber, GP4 to BS7655:section 1.2

Inner sheath: No inner sheath, additional tapes may be applied

Armour/screen: No armour

Outer sheath: Flame retardant, halogen-free, enhanced oil resisting thermoset compound (LSF) SW4 to BS7655 section 2.6. (Mud resistant version available on request)

Marking text: "meter mark" "year" "DRAKA" "RU" "UKOOA code"  "600/1000V" "number of cores" "conductor size" "BS6883" "IEC60332-3-32" (marking may differ on cable actually supplied)

Outer sheath colour: Black

Core identification: All cores are offwhite with black numbers No 1,2,3....

Operating tempeature: 90°C

Operating Voltage: 0.6/1kV

Description:
• RU 0.6/1kV 2X 1.5mm2
• RU 0.6/1kV 2X 2.5mm2
• RU 0.6/1kV 3X 1.5mm2
• RU 0.6/1kV 3X 2.5mm2
• RU 0.6/1kV 3X 4mm2
• RU 0.6/1kV 3X 6mm2
• RU 0.6/1kV 3X 10mm2
• RU 0.6/1kV 3X 16mm2
• RU 0.6/1kV 4X 1.5mm2
• RU 0.6/1kV 4X 2.5mm2

Sheath Colour: BLACK

Design standard: BS 6883:1999

Standards applied:
• BS6883 - Design
• BS6360 class 2 - Conductor
• BS7655 section 1.2 - Insulation
• BS7655 section 2.6 - Sheath
• IEC 60332-1 - Flame Retardant
• IEC60332-3-22 - Flame retardant
• IEC60754-1,2 - Halogen Free
• IEC 61034-1,2 - Low Smoke

Application:
• Unarmoured cable for fixed installation where cable protection is not required. Power, control and lighting in safe areas.
• Enhanced MUD resistant version also available for use in areas exposed to mud and drilling / cleaning fluids, meeting the mud resistance requirement n NEK 606.

technical specification:
number of cores 2
cross section core, mm2 2.5
conductor diameter, mm 2
insulation thickness, mm 0.8
thickness outer sheath, mm 1.1
approx. overall diameter, mm 9.5
approx. weight of cable (kg/km) 150
copper content approx. (kg/km) 46
max. conductor resistance at 20°c, ohm/km 7.56
max. conductor resistance at 90°c, ohm/km 9.64
reactance at 50hz, ohm/km 0.096
reactance at 60hz, ohm/km 0.115
current rating iec 60092-352 table b.4, ampere 26
short circuit rating 1 second, ampere 350
prysmian and draka cable part number 840301

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question