Prysmian Cable 2 Solid 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8301ZC
Select gauge from drop-down menu for prices:
- Prysmian Cable 15kV 133% Copper TRXLPE URD CSA Medium Voltage Utility Cables
- Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8401ZC
- Prysmian Cable 1 Solid 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8501ZC
- Prysmian Cable 1 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8601ZC
- Prysmian Cable 1/0 Solid 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8701ZC
- Prysmian Cable 1/0 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8801ZC
- Prysmian Cable 2/0 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8901ZC
- Prysmian Cable 2 Solid 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8300ZC
- Prysmian Cable 2 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8400ZC
- Prysmian Cable 1 Solid 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8500ZC
- Prysmian Cable 1 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8600ZC
- Prysmian Cable 3/0 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8A01ZC
- Prysmian Cable 4/0 AWG 15kV 133% Copper TRXLPE URD CSA Single Phase Full Neutral Medium Voltage Utility Cables Q8B01ZC
- Prysmian Cable 1/0 Solid 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8700ZC
- Prysmian Cable 1/0 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8800ZC
- Prysmian Cable 2/0 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8900ZC
- Prysmian Cable 3/0 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8A00ZC
- Prysmian Cable 4/0 AWG 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8B00ZC
- Prysmian Cable 250 MCM 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8C00ZC
- Prysmian Cable 350 MCM 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8D00ZC
- Prysmian Cable 500 MCM 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8E00ZC
- Prysmian Cable 750 MCM 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8F00XC
- Prysmian Cable 1000 MCM 15kV 133% Copper TRXLPE URD CSA Three Phase One Third Neutral Medium Voltage Utility Cables Q8G00XC
Conductor: Solid or Class B compact or compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.
Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes.
Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.
Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• EPROTENAX™ (EPR) insulation
• Multiplex cables
• Tinned round and flat strap neutrals
• Strandseal®
• Super smooth conductor shield
• Cables made to AEIC CS8 and/or ICEA S-94-649
• 46kV
Installations:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary
Specifications and Ratings:
• CSA - CSA C68.5 -40°C
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.
technical specifications: | |
conductor | 2 Solid cu |
insulation thickness (mils) | 220 |
concentric neutral | 16-#14 |
conductor diameter (in) - (a) | 6.55 |
insulation diameter (in) - (b) | 19.10 |
insulation shield diameter (in) - (c) | 20.98 |
jacket diameter (in) - (d) | 27.08 |
cable weight (lbs/kft) | 1082 |
minimum bending radius (in) | 229 |
† ampacity (amps) - 90°c in duct | 157 |
+/- sequence impedance resistance (µΩ/ft) - 90°c in duct | 1.34 |
+/- sequence impedance reactance (µΩ/ft) - 90°c in duct | 0.10 |
zero sequence impedance resistance (µΩ/ft)†† - 90°c in duct | 1.34 |
zero sequence impedance reactance (µΩ/ft)†† - 90°c in duct
|
0.10 |
† ampacity (amps) - 90°c direct buried | 215 |
+/- sequence impedance resistance (µΩ/ft) - 90°c direct buried | 1.34 |
+/- sequence impedance reactance (µΩ/ft) - 90°c direct buried | 0.10 |
zero sequence impedance resistance (µΩ/ft)†† - 90°c direct buried | 1.34 |
zero sequence impedance reactance (µΩ/ft)††- 90°c direct buried | 0.10 |
prysmian cable part number | Q8301ZC |