Amercable Tiger Brand 2/0 AWG Type MP-GC 3/C Mine Power Feeder 5kV PVC Jacket 100% Level Grounded Cable 36-621-020

Amercable Tiger Brand 2/0 AWG Type MP-GC 3/C Mine Power Feeder 5kV PVC Jacket 100% Level Grounded Cable 36-621-020

Select gauge from drop-down menu for prices:

Amercable Tiger Brand 2/0 AWG Type MP-GC 3/C Mine Power Feeder 5kV PVC Jacket 100% Level Grounded Cable 36-621-020

Product Details

Conductors: Copper 

Insulation: 90°C ethylene-propylene rubber (EPR) 

Ground Wires: Tinned copper 

Strand Shield: Semi-conducting layer 

Ground Check Conductor: 8 AWG 7-wire copper with yellow polypropylene insulation 

Jacket:
• 36-601: Mold-cured thermosetting Chlorinated Polyethylene (CPE) Jacket. Cable identification via permanent marking.
• 36-621: Polyvinyl chloride (PVC), cable identification via permanent surface marking. 

Insulation Shielding: Semi-conducting layer under copper tape (phase identification provided) 

Assembly: Taped core 

Application: 
• Connections between units of mine distribution systems not exceeding the rated voltage when installed in duct, conduit or open air and for direct burial in wet and dry locations. Recommended maximum continuous conductor temperature is 90°C. 
• Cable carries “P-7K-184-MSHA” marking indicating listing by the Mine Safety and Health Administration and the Pennsylvania Department of Environmental Protection. 
• Tiger® Brand Mining Cable meets or exceeds ICEA Standards S-75-381/NEMA WC-58, ASTM B-8 and B-33. 

Ratings & Approvals:
36-601:
• Mine Safety & Health Administration 7K-184-MSHA.
• Pennsylvania Department of Environmental Protection P-7K-184.
• Insulated Cable Engineers Association S-75-381. Design standard for mining cables.
36-621:
• Mine Safety & Health Administration 7K-184-MSHA.
• Pennsylvania Department of Environmental Protection P-7K-184.
• Tiger® Brand Mining Cables meet or exceed ICEA Standards S-75-381 & CSA Standards C 22.2 #96.1
• Canadian Standards Association File 82346, FT1, FT5, -35°C Type MP-GC, MPF up to 25kV

technical specification:
power conductors - size awg 2/0
power conductors - no. of wires per conductor 19
power conductors - insulation thickness mils 90
grounding conductors -size awg 3
grounding conductors - no. of wires per conductor 7
jacket thickness mils 110
nominal outside dimensions in. 1.88
approx. weight lbs. per 1,000 ft. 2721
ampacity*40°c ambient temp 243
amercable and tiger brand part number 36-621-020

QUESTIONS & ANSWERS