General Cable Duralox Uniblend® 350MCM Type MV-105 or MC 3C 220 Mils EPR AIA PVC Power Shielded Armored with Enhanced Ground Wires (50%) UL

General Cable Duralox Uniblend® 350MCM Type MV-105 or MC 3C 220 Mils EPR AIA PVC Power Shielded Armored with Enhanced Ground Wires (50%) UL

Product Details

Conductors: 1/0 AWG thru 1000 kcmil bare, copper compact Class B strand

Extruded Strand Shield (ESS): Thermoset semi-conducting extruded stress control layer over conductor

Insulation: Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers

Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer free stripping from insulation

Shield: 5 mil annealed copper tape with a minimum 25% overlap

Ground: Annealed bare copper Class B stranding per ASTM B8

Armor: Aluminum Interlocked Armor (AIA)

Jacket: Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), red

Options: Galvanized Steel Interlocked Armor (GSIA)

Applications:
• Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance is demanded, space is limited, ease of installation is critical and fire resistance is necessary
• Installed in wet or dry locations, indoors or outdoors, in exposed or concealed work
• May be used in cable trays or on approved support in protected areas
• Permitted for use per NEC Article 334
- Class I, Division 2
- Class II, Division 2
- Class III, Divisions 1 and 2

Features:
• Rated at 105?C wet or dry
• Excellent heat and moisture resistance
• Outstanding corona resistance
• Flexibility for easy handling
• High dielectric strength
• Low moisture absorption
• Electrical stability under stress
• Low dielectric loss
• Chemical- and radiation-resistant
• Excellent crush resistance
• Cost-effective alternative to installations in conduit
• Meets cold bend test at -40?C
• 105°C rating for continuous operation
• 140°C rating for emergency overload conditions
• 250°C rating for short circuit conditions

Compliances:
Industry Compliances:
• UL 1072
• ICEA S-93-639/NEMA WC74
• AEIC CS8
• UL Type MV-105, UL File # E90501
• UL Type MC, UL File # E90496

Flame Test Compliances:
• IEEE 383 (70,000 BTU/hr)
• UL 1581 (70,000 BTU/hr)
• IEEE 1202 (70,000 BTU/hr) CSA FT4
• ICEA T-29-520 (210,000 BTU/hr)
• ICEA T-30-520 (70,000 BTU/hr)

Other Compliances:
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
• RoHS Compliant

Packaging: Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

technical specification
cond. size(awg/kcmil) 350
no. of cond. 3
cond. dia. inches 0.62
insulation diameter(min. in inches) 1.07
insulation diameter(min.in mm) 27.2
insulation diameter(max.in inches) 1.16
insulation diameter(max.in mm) 29.4
grnd. wire size (awg) 3x2
nom. dia. (over) armor(inches) 2.85
nom. dia. (over) armor(mm) 72.4
nominal jacket thickness(inches) 0.075
nominal jacket thickness(mm) 1.91
nominal cable o.d.(inches) 3.01
nominal cable o.d.(mm) 76.6
copper weight(lbs/1000ft) 4212
copper weight(kg/km) 6272
net weightw/al armor(lbs/1000ft) 6674
net weight w/al armor(kg/km) 9938
catalog number 17476.516200*

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question