General Cable NextGen® Loose Tube 2 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
Select gauge from drop-down menu for prices:
- General Cable NextGen® Loose Tube Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 4 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 6 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 8 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 12 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 18 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 24 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 36 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 48 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 60 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 72 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 96 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
- General Cable NextGen® Loose Tube 144 Fiber Count Single Jacket Plenum Indoor/Outdoor Fiber Optic Cable Type OFNP CSA FT6
Fiber:
• 2–144 fibers
• Dry loose tube with super-absorbent polymer
• Color-coding per TIA/EIA 598 B
Central Strength Member: Epoxy/glass rod
Overall Strength Member: Aramid fiber yarn
Jacket: Sequential footage markings*
Options:
• Interlock steel or aluminum (-ILP or -ILPA)
• Dry Water Block cable core for ease of handling (gel tubes)
Features:
• Loose tube plenum design provides maximum cable route flexibility
• Dry loose tube for ease of termination
• Excellent chemical-resistant cable for harsh industrial environments
Performance:
• Temperature:
Storage -40°C (-40°F) to +70°C (+158°F)
Installation 0°C (+32°F) to +50°C (+122°F)
Operating -20°C (-4°F) to +70°C (+158°F)
• Minimum Bend Radius:
20 X OD—Installation
10 X OD—In-Service
• Maximum Crush Resistance: 150 lbs/in (263 N/cm)
Applications:
• Interbuilding and intrabuilding voice or data communication backbones
• Install in ducts, underground conduits or aerial/lashed
• ETL Listed Type OFNP for installation in plenum airways and horizontal applications when installed in accordance with NEC article 770.154 and 770.179
Compliances:
• ETL Listed Type OFNP
• CSA FT6
• ICEA S-104-696
• RoHS Compliant Directive 2011/65/EU
technical specification: | |
fiber count | 2 |
no. of loose tubes | 2 |
nominal cable diameter(in) | 0.31 |
nominal cable diameter(mm) | 8 |
nominal cable weight(lbs/1000') | 46 |
nominal cable weight(kg/km)
|
69 |
maximum tensile load(installation in lbs) | 300 |
maximum tensile load(installation in n) | 1334 |
maximum tensile load (in-service in lbs) | 100 |
maximum tensile load(in-service in n) | 445 |
catalog number | XX0023M1D-DT |