Single conductor cable with stranded copper conductor, extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX® EPR insulation, thermosetting semiconducting insulation shield, helically applied bare copper tape shield, separator tape, foamed polymeric Air Bag™ layer for superior mechanical protection, a Drylam® layer consisting of a longitudinally applied aluminum tape and an extruded oil and hydrocarbon resistant polymer, and overall non-leaded sun resistant PVC jacket.

Specifications:
• CSA -CSA C68.10
• CSA - C22.2 No.0.3
• CSA - C22.2 No. 230

Ratings:
• Cold Impact/Bend Test (-40°C) 105°C
• Sunlight Resistant FT4
• TC (1/0 AWG and Larger)

Conductor: Class B Compact concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength EPROTENAX® EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Helically applied non-magnetic copper tape(s) over the insulation shield followed by a separator tape.

Mechanical Protection: High strength and high crush resistant Air Bag™ Layer extruded over the core.

Chemical Protection: A layer of Drylam® which consists of an aluminum tape a chemical resistant extruded polymer layer is applied.

Jacket: Sunlight resistant polyvinyl chloride (PVC), non-leaded jacket.

technical specification
conductor size 1/0 AWG CU
insulation thickness (mils) 320
conductor diameter (mm) 8.66
insulation diameter (mm) 25.98
insulation shield diameter (mm) 27.41
overall jacket diameter (mm) 37.44
cable weight (lkg/km) 1746
minimum bending radius (mm) 450
ampacity in air and cable tray‡105°c 290
impedance in air and cable tray (μω/m) pos/neg seq 452 + j253
impedance in air and cable tray (μω/m)zero seq 2085 + j109
prysmian cable part number QXM241A