Technical Specifications: | |
Size (AWG or kcmil): | 2 |
No. of Strands | 7 |
Insulation Thickness Mils | 220 |
Jacket Thickness (Mils): | 80 |
Insulation Diameter (Inches): | 0.76 |
Drain Wire Size AWG | 19 |
Conductor Diameter (Inches): | 0.27 |
Overall Diameter (Inches): | 0.94 |
Net Weight (lbs.): | 574 |
Specifications:
- HW210
- Power Cable - Unishield
- 15KV UL Type MV-105, 105°C
- Single Conductor, Shielded
- EPR Insulation, CPE Jacket
- 133% Insulation Level
- Copper Conductor
Application:
For use in power circuits up to 15KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for critical applications in harsh and caustic environments in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
Compact soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-496, with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682.
Shield:
Six (6) corrugated copper shield wires longitudinally embedded in an exterior semi-conducting CPE jacket per ICEA S-97-682.
Jacket:
Sunlight-resistant CPE per ICEA S-97-682 and UL Standard 1072.
Flame Tests:
- IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger
- IEEE1202 70,000 BTU/hr, CSA FT4 flame test
- ICEA T-29-520 210,000 BTU/hr flame test
Additional Standards:
- ICEA S-93-639
- NEMA WC74
- AEIC CS8
Note:
- CT rated on sizes 1/0 AWG and larger.