Superior Essex Cable 14 AWG 37 Conductor PVC/Nylon/PVC 600V Control Type TC-ER Unshielded Cable E2BEA-141B37CB00

Superior Essex Cable 14 AWG 37 Conductor PVC/Nylon/PVC 600V Control Type TC-ER Unshielded Cable E2BEA-141B37CB00

Select gauge from drop-down menu for prices:

Superior Essex Cable 14 AWG 37 Conductor PVC/Nylon/PVC 600V Control Type TC-ER Unshielded Cable E2BEA-141B37CB00

Product Details

Superior Essex Cable 14 AWG 37 Conductor PVC/Nylon/PVC 600V Control Type TC-ER Unshielded Cable E2BEA-141B37CB00

The Superior Essex PVC/Nylon/PVC, 600V Control, Type TC-ER Cables consist of fully annealed bare copper Class B stranded conductors, covered with Polyvinyl Chloride (PVC) and clear Nylon insulation, unshielded or shielded and black PVC jacket. These cables are used in industrial power or station control circuits.

Features:
• Rated at 75°C wet or 90°C dry
• Ripcord (for jackets with thicknesses of 60-mils or less)
• Excellent sunlight resistance
• Smallest OD available for suitable applications
• Meets cold bend test at -25°C

Specifications:
Conductor Count: Available in 2 through 37 conductors

Conductor: Fully annealed bare copper Class B compressed strand

Gauge Sizes: Available in 18 through 10 AWG

Insulation: Polyvinyl Chloride (PVC) covered with Nylon
• 18 through 16 AWG are type TFN
• 14 AWG and larger are type THHN/THWN

Color Coding: Per ICEA S-58-679 Method 1, Table E-1; additional color coding options available

Fillers: Non-hygroscopic fillers, as necessary to obtain a circular cross section

Shield (optional): Overall aluminum polyester (mylar) foil in contact with 20 AWG stranded tinned copper drain wire

Jacket: Polyvinyl Chloride (PVC)

Jacket Marking: 

Type TC-ER, conductor sizes 18 AWG – 16 AWG: 00000 FT SUPERIOR ESSEX XXAWG XX/C PVC/NYLON PVC JKT 600V 75C WET OR 90C DRY TYPE TC-ER (UL) SUN RES DIR BUR FT4/IEEE1202 MADE IN USA MMDDYYYY

Type TC-ER, conductor sizes 14 AWG – 10 AWG: 00000 FT SUPERIOR ESSEX XXAWG XX/C THHN/THWN PVC JKT 600V 75C WET OR 90C DRY TYPE TC-ER (UL) SUN RES DIR BUR FT4/IEEE1202 MADE IN USA MMDDYYYY

Packaging: Non-returnable wood reels in a variety of lengths and dimensions

Performance Compliances: 
• ASTM B8, ASTM B33
• UL® 66, UL 83, UL 1277, UL 1685 (flame compliance)
• ICEA S-95-658, ICEA S-73-532
• CSA FT4/IEEE1202 (flame compliance)
• NEC

Other Compliances: 
• EPA 40 CFR, Part 261
• OSHA
• RoHS-compliant/RoHS 2-compliant
• REACH-compliant

Applications:
• In conduit, duct, free air, raceways and direct burial, primary installations include cable trays, and outdoor    locations
• In wet or dry locations
• Approved for Class I, Div. 2 industrial hazardous locations per NEC
• Permitted for Exposed Run (ER) used in accordance with NEC for 3 or more conductors; two conductors    without a ground wire are Type TC only

technical specification:
conductor size awg 14
conductor count conductor 37
nominal insulation thickness¹ in (mm) 0.020 (0.51)
nominal jacket thickness¹ in (mm) 0.080 (2.03)
nominal overall diameter¹ in (mm) 0.970 (24.64)
nominal net weight¹ lbs/kft (kg/km) 766 (1,140)
superior essex cable part number E2BEA-141B37CB00