Product Details
Superior Essex Cable 14 AWG 30 Conductor PVC/Nylon/PVC 600V Control Type TC-ER Unshielded Cable E2BEA-141B30CB00The Superior Essex PVC/Nylon/PVC, 600V Control, Type TC-ER Cables consist of fully annealed bare copper Class B stranded conductors, covered with Polyvinyl Chloride (PVC) and clear Nylon insulation, unshielded or shielded and black PVC jacket. These cables are used in industrial power or station control circuits.
Features:
• Rated at 75°C wet or 90°C dry
• Ripcord (for jackets with thicknesses of 60-mils or less)
• Excellent sunlight resistance
• Smallest OD available for suitable applications
• Meets cold bend test at -25°C
Specifications:
Conductor Count: Available in 2 through 37 conductors
Conductor: Fully annealed bare copper Class B compressed strand
Gauge Sizes: Available in 18 through 10 AWG
Insulation: Polyvinyl Chloride (PVC) covered with Nylon
• 18 through 16 AWG are type TFN
• 14 AWG and larger are type THHN/THWN
Color Coding: Per ICEA S-58-679 Method 1, Table E-1; additional color coding options available
Fillers: Non-hygroscopic fillers, as necessary to obtain a circular cross section
Shield (optional): Overall aluminum polyester (mylar) foil in contact with 20 AWG stranded tinned copper drain wire
Jacket: Polyvinyl Chloride (PVC)
Jacket Marking:Type TC-ER, conductor sizes 18 AWG – 16 AWG: 00000 FT SUPERIOR ESSEX XXAWG XX/C PVC/NYLON PVC JKT 600V 75C WET OR 90C DRY TYPE TC-ER (UL) SUN RES DIR BUR FT4/IEEE1202 MADE IN USA MMDDYYYY
Type TC-ER, conductor sizes 14 AWG – 10 AWG: 00000 FT SUPERIOR ESSEX XXAWG XX/C THHN/THWN PVC JKT 600V 75C WET OR 90C DRY TYPE TC-ER (UL) SUN RES DIR BUR FT4/IEEE1202 MADE IN USA MMDDYYYY
Packaging: Non-returnable wood reels in a variety of lengths and dimensions
Performance Compliances:
• ASTM B8, ASTM B33
• UL® 66, UL 83, UL 1277, UL 1685 (flame compliance)
• ICEA S-95-658, ICEA S-73-532
• CSA FT4/IEEE1202 (flame compliance)
• NEC
Other Compliances:
• EPA 40 CFR, Part 261
• OSHA
• RoHS-compliant/RoHS 2-compliant
• REACH-compliant
Applications:
• In conduit, duct, free air, raceways and direct burial, primary installations include cable trays, and outdoor locations
• In wet or dry locations
• Approved for Class I, Div. 2 industrial hazardous locations per NEC
• Permitted for Exposed Run (ER) used in accordance with NEC for 3 or more conductors; two conductors without a ground wire are Type TC only
technical specification: | |
conductor size awg | 14 |
conductor count conductor | 30 |
nominal insulation thickness¹ in (mm) | 0.020 (0.51) |
nominal jacket thickness¹ in (mm) | 0.080 (2.03) |
nominal overall diameter¹ in (mm) | 0.932 (23.67) |
nominal net weight¹ lbs/kft (kg/km) | 639 (954) |
superior essex cable part number | E2BEA-141B30CB00 |