Conductor: 10 AWG bare copper Class B compressed concentric round to ASTM B8
Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 1 to 4 conductors— black, white, red and blue; over 4 conductors—per ICEA Method 4, individual conductors colored black with conductor number surface printed in contrasting ink
Ground (Bonding)Conductor:
• The conductor consists of one uninsulated stranded bare copper conductor
• Color-coded per ICEA Method 4; individual conductors colored black with conductor number surface printed in contrasting ink
Inner Jacket: Lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
Armor: Aluminum Interlocked Armor (AIA)
Overall Jacket: Lead-free, ACID-FLAME-CHECK ??® flameretardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armor (GSIA)
Applications:
• For exposed and concealed wiring in dry, damp or wet locations
• For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required by inspection authority)
• For wiring in all hazardous locations when used with certified HL cable glands
Features:
• Rated at 90?C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Meets cold bend and impact tests at -40?C
Compliances:
Industry Compliances: CSA Standard C22.2 No. 131 and No. 174
Flame Test Compliances:
• CSA FT1 and FT4
• IEEE 383 (70,000 BTU/hr)
• UL 1581 (70,000 BTU/hr)
• IEEE 1202 (70,000 BTU/hr) CSA FT4
• ICEA T-30-520 (70,000 BTU/hr)
Other Compliances:
• Hazardous Location Rating: HL
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
• RoHS Compliant
Packaging:
• For Canadian customers, lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for lagging, pulling eyes, paralleling and plexing
• For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing
technical specification: | |
cond. size (awg) | 10 |
no. of cond. | 6 |
ground wire size (awg) | 12 |
nominal diameter (over)(insulation in inches) | 0.18 |
nominal diameter (over)(insulation in mm) | 4.5 |
nominal diameter (over)(armor in inches) | 0.88 |
nominal diameter (over)(armor in mm) | 22.2 |
nominal diameter (over)(cable in inches) | 0.96 |
nominal diameter (over)(cable in mm) | 24.3 |
copper weight(lbs/1000ft) | 217 |
copperweight(kg/km) | 323 |
net weight w/armor(lbs/1000ft in al) | 515 |
net weight w/armor(lbs/1000ft in steel) | 717 |
net weight w/armor(kg/km in al) | 766 |
net weight w/armor(kg/km in steel) | 1066 |
ampacity** (30?c ambient) | 32 |
catalog number | 333160* |