350-3 VFDTC Tray Cable

350-3 VFDTC Tray Cable

Product Details

Technical Specifications:
Number of Conductors in Cable: 3
Jacket Thickness (mils): 110
Nominal Insulation Thickness (mm): 65
Ground Wire Size (AWG): 3-#2
Size AWG: 350
Stranding: 37
Diameter Complete Cable (O.D.) (Inches): 1.983
Weight Per 1000ft Total (Lbs.): 4,898
Allowable Ampacity 30C (Amps): 350

350-3 ASD-VFD Tray Cable

The 350-3 ASD-VFD tray cable is designed for use in ASD /VFD applications. These cables meet UL Standard 1277 and are flame rated according to a number of different regulations:

  • IEEE 383
  • ICEA T-29-520
  • IEEE 1202 / CSA FT-4
  • These cables are also rated for CT use and for direct burial.
  • RoHS compliant

These cables meet all applicable guidelines of the National Electrical Code.

Description:

3 conductors, stranded, insulated with heat and moisture resistant cross-linked polyethylene, phase identified, cabled together with suitable fillers and 3 symmetrical bare copper ground conductors. Cable core covered with 5-mil helical copper tape shield, and overall flame and sunlight resistant black PVC jacket. Surface printed. Jacket available in colors.

Features:

  • Suitable for use in NEC Hazardous Locations: Class I - Div 2, Class II - Div 2, and Class III, Div 1 and 2.
  • For use in ASD / VFD applications.
  • Standards: UL 1277
  • Flame Rated: IEEE 383 (70,000 BTU), ICEA T-29-520 (210,000 BTU) on 1/0 and larger IEEE 1202 / CSA FT-4 Two-hour Firewall rated, (2/0 AWG and smaller)Sunlight Resistant, for CT Use; Direct Burial Oil Resistant II
  • JacketCode: Black and Numbered
  • Temperature Rating: 90?C Wet / Dry ICEA S-95-658 / NEMA WC-70
  • Exposed runs rated #4 and larger 600 Volt Tray Cable RoHS Compliant.

Specifications:

The 350-3 cable features three stranded conductors with a size of 350 AWG. It has a stranding (Al/Stl) of 37. This cable also features 3 symmetrical bare copper ground wires that are 2 AWG in size. The cable core is covered with a special 5-mil helical copper tape shield. This is in addition to the cross-linked polyethylene insulation. This insulation has a nominal thickness of 65 mm and is moisture and heat resistant. A black PVC jacket provides an outer layer of protection and is resistant to flame, sunlight, and abrasions. While black is standard, other colors can be substituted for easy identification.

The overall cable diameter for this cable is 1.983 inches. This cable has an allowable ampacity of 350 amps at 30 degrees C and weighs 4,898 pounds in lengths of 1,000 feet. It is rated for 600 volts.

Applications:

ASD-VFD cables such as the 350-3 cable are used in a number of different applications involving motors. They connect Variable Frequency Drives (VFDs) to AC motors. A VFD is an adjustable-speed drive that’s used in a number of different electro-mechanical drive systems to control the speed of the AC motor and the torque. It varies the voltage and the motor input frequency. Doing so helps conserve power and improve performance. These cables can be used with motors that control water pumps, fan motors, conveyor motors, and more.

These cables can be used in a number of places designated as NEC Hazardous Locations, including those designed as Class I, Division 2, Class II, Division 2, and Class III, Divisions I and II. It may be used in wet or dry areas where the operating temperature does not exceed 90 degrees C.